ADPS

ADJUSTABLE DEADBAND

PRESSURE SWITCH

MOUNTING AND INSTALLATION

The Model ADPS is typically mounted in an upright position on a flat surface by two 1/4" screws
through the mounting flanges on the base or by two 1/4-20 screws into the back of the base.
See Fig. 1 for mounting dimensions. Locate the switch where vibration, shock and ambient
temperature fluctuations are minimal. To avoid damage to the switch, always hold a wrench
on the pressure connection hex when tightening pressure connections. Never tighten the
pressure connection by turning the switch housing into the fitting.

FIG. 1

WIRING

Use properly rated temperature supply wire for the anticipated service temperature. Make all
electrical connections in accordance with the National Electrical Code and local regulations.
A wiring check may be performed by manually actuating the switch actuator on the side of the
snap-action switch inside the enclosure. (See Fig. 3) 

NOTE:

 Do not loosen or remove the two (2)

screws that secure the switch to the switch mounting bracket.

4.47

.88

1.66

3.26

5.41

2.25

1.33

DWG. #1080-1

(2) 

1

4

-20 x .50 DEEP

THREADED HOLES FOR

BACK MOUNTING OPTION

(1) Ø.875 HOLE

FOR 

1

2

" CONDUIT

CONNECTION

3.38

(2) Ø.266 MOUNTING

THRU HOLES

FOR 

1

4

" SCREWS

.94

4.65

COM.

N.C.

N.O.

N.O.

N.C.

COM.

DWG. #1060-2

SWITCH ACTION ON

(OPERATING POINT)

HIGH PRESSURE

(RESET POINT)

LOW PRESSURE

SWITCH ACTION ON

N.C.

N.O.

COM. 

N.C.

N.O.

COM. 

FIG. 2

Содержание ADPS Series

Страница 1: ...e entire operating range of the switch The mini mum deadband minimum span between set and reset points may be obtained at any point in the operating range of the switch A change in pressure greater than the high setting will reposition the switch mechanism to open or close a single snap action electrical switch This control device is designed for use as an operating control in applications sensing...

Страница 2: ...ousing into the fitting FIG 1 WIRING Use properly rated temperature supply wire for the anticipated service temperature Make all electrical connections in accordance with the National Electrical Code and local regulations A wiring check may be performed by manually actuating the switch actuator on the side of the snap actionswitchinsidetheenclosure SeeFig 3 NOTE Donotloosenorremovethetwo 2 screws ...

Страница 3: ...ure en countered in the application The minimum deadband minimum span be tween set and reset points may be obtained at any point in the operating range of the switch When the desired settings are obtained re place the adjustment cover The adjustment cover and enclosure cover can be made tamper resistant by a single sealing wire inserted through the hole in the locking bar The repeatability of the ...

Страница 4: ... COPPER 1370020 ADPS 300 1S 25 300 PSIG 12 PSIG 400 PSIG 1 4 NPT 316 S S BERYLLIUM COPPER W 316 S S ISOLATOR 1370030 ADPS 300 2S 25 300 PSIG 12 PSIG 400 PSIG 3 8 NPT 316 S S BERYLLIUM COPPER W 316 S S ISOLATOR 1370040 ADPS 600 1B 50 600 PSIG 25 PSIG 650 PSIG 1 4 NPT BRASS BERYLLIUM COPPER 1370050 ADPS 600 1S 50 600 PSIG 25 PSIG 650 PSIG 1 4 NPT 316 S S BERYLLIUM COPPER W 316 S S ISOLATOR 1370060 A...

Отзывы: