3.8
CHECKING FOR CLEARANCE OF COMBUSTION PRODUCTS
3.8.1
Close all doors and windows in the room.
3.8.2
Light the stove and allow to run for approximately 5 minutes on high
position.
3.8.3
After approximately 5 minutes hold a smoke match just inside and
10mm below the top edge of the draft diverter (located on the rear of
right hand side of the stove as shown below in figure 36). A suitable
smoke match holder must be used when checking for clearance of
combustion products). All smoke generated should be drawn back into
the flue. If slight spillage occurs or if in doubt, repeat the test after a
further 5-10 minutes.
If the test indicates that spillage is occurring
and the flue restrictor baffle has been fitted, it should be removed
and the test repeated after the fire has cooled.
Fig. 36
3.8.4
If spillage persists, the flue is not functioning correctly and a fault exists.
If, after investigation the fault cannot be traced and rectified, the fire
must be disconnected from the gas supply and expert advice obtained.
3.8.5
If there is an extractor fan fitted any where in the vicinity of the
appliance, the spillage test should be repeated with the fan running on
maximum and all interconnecting doors open.
3.8.6
After ensuring that the fire is safe to use it should be left on high
position to fully warm up. During this time a slight odour may be
noticed, this is due to the “newness” of the fire and will soon disappear.
Finally, hand this manual over to the customer and explain the operation
of the fire.
37
Smoke match position :-
Approximately 10mm below
centre of draft diverter