Basic Installation and  
Configuration Guidelines 

Use minimum 6AWG copper conductors only.
Torque field connections between 21 and 23 in lbs.
Readily accessible disconnecting means to be provided at time of instal-
lation.
Permanently connected.
Connect only to a circuit protected by a Class A Ground Fault Circuit  
Interrupter (GFCI) or Residual Current Device (RCD) mounted at least 5’ 
(1.52M) from the inside walls of the spa/hot tub and in line of sight from 
the equipment compartment.
CSA enclosure: Type 2
Refer to Wiring Diagram inside the cover of the control enclosure.
Refer to Installation and Safety Instructions provided by the spa manufac-
turer.

Warning: 

People with infectious diseases should not use a spa or hot

tub.

Warning: 

To avoid injury, exercise care when entering or exiting the spa

or hot tub.

Warning: 

Do not use a spa or hot tub immediately following strenuous

exercise

Warning: 

Prolonged immersion in a spa or hot tub may be injurious to

your health

Warning: 

Maintain water chemistry in accordance with the Manufactur-

ers instructions.

Warning: 

The equipment and controls shall be located not less than 1.5

meters horizontally from the spa or hot tub.

Warning! GFCI or RCD Protection.

The Owner should test and reset the GFCI or RCD on a 
regular basis to verify its function.

CSA Compliance/Conformité

Caution:

Test the ground fault circuit interrupter or residual current device before

each use of the spa.

• Read t

he instruction manual.

Adequate drainage must be provided if the equipment is to be installed

in a pit.

• For use only within an e

nclosure rated CSA Enclosure 3.

• Con

nect only to a circuit protected by a Class A ground fault circuit

interrupter or residual current device.

To ensure continued protection against shock hazard, use only identical

replacement parts when servicing.

marked.
Warning:

Water temperature in excess of 38°C may be injurious to your health.

• Discon

nect the electrical power before servicing.

Attention:

differentiel avant d’utiliser le bain.

• Li

re la notice technique.

• Lorsque l’appa

reillage est installe dans une fosse, on doit assurer un

drainage adequat.

• Employer unique

ment a l’interieur d’une cloture CSA Enclosure 3.

• Con

necter uniquement a un circuit protege par un disjoncteur differen-

tiel de Class A.

electrique, lors de l’entretien employer seulement des pieces de rechange 
identiques.

• Les prises d’aspi

ration doivent etre equipees de grilles convenant au

debit maximal indique.

Avertissement:

• Des tempe

ratures de l’eau superieures a 38°C peuvent presenter un

danger pour la sante.

• Decon

necter du circuit d’alimentation electrique avante l’entretien.

Warning/Advertissement:

• Discon

nect the electric power before servicing. Keep access door closed.

• Decon

necter du circuit d’alimentation electrique avant l’entretien.

Garder la porte fermer.

Warning!  Qualified Technician Required for Service and Installation

Warning! Shock Hazard!  
No User Serviceable Parts.

Do not attempt service of this control system. Contact your 
dealer or service  organization for assistance. Follow all 
owner’s manual power connection  instructions. Installation 
must be performed by a licensed electrician and all ground-
ing connections must be properly installed.

30

Содержание OS030994B

Страница 1: ...Article No OS030994B PRODUCT MANUAL...

Страница 2: ...l it up 8 5 3 Spa Behavior 9 5 4 Temperature and Temp Range 10 5 5 Mode Ready and Rest 11 5 6 Show and Set Time of Day 12 5 7 Flip Invert Display 12 5 8 Restricting Operation 13 5 9 Unlocking 13 5 10...

Страница 3: ...rs or bricks or a reinforced deck The adequacy of the structural support for a spa placed on a terrace balcony roof terrace or other elevated structure must be determined by a licensed structural engi...

Страница 4: ...ructure of the SPA Size 2310 1960 890mm Pillow 4pcs Shell Aristech Acrylic White Number of Seats 6 PS Skirt Grey 5 rotating jet 4pcs Filter 1pc 3 5 jet 4pcs LED Light 2pcs 3 4 jet 33pcs Ozone 1pc Air...

Страница 5: ...located inside the removable skirt board You will find the following stickers on the board To open the skirt board you need a pliers and a screwdriver 1 Remove the gray screw cap at the bottom of the...

Страница 6: ...ected to the fire wire BRN 1 the third interface is connected to the neutral wire BLU and the fourth interface is connected to the fire wire BRN 2 The ground wire needs to be connected to the second i...

Страница 7: ...level marker on your tub as picture below and make sure the water is filled up within the standard range Start all the pumps to test the system See section 5 for the system instruction Put the filter...

Страница 8: ...ser Interface and Programming Reference Standard Menus System Model Software Version BP Series Systems BP6013G2 7 0 and later Panel Model TP600 Series Software Version 2 3 or later JETS AUX LIGHT HEAT...

Страница 9: ...The LIGHT Button is also used to choose the various menus and navigate each section Typical use of the Temperature button s allows changing the Set Temperature while the numbers are flashing in the L...

Страница 10: ...pumps have not primed after 2 minutes and water is not flowing from the jets in the spa do not allow the pumps to continue to run Turn off the pumps and repeat the process Note Turning the power off a...

Страница 11: ...h the circulation pump The system is factory programmed with one filter cycle that will run in the evening assuming the time of day is properly set when energy rates are often lower The filter time an...

Страница 12: ...cturer Freeze Protection is active in either range See Ready and Rest on Page 6 Temperature and Temp Range 04 1 1 09 Sub Menu Detail Set Temperature and Water Temperature Ranges High Range via Low Ran...

Страница 13: ...creen will show ACTIVATE PUMP FOR TEMPERATURE if the filtration pump has not been running for more than an hour The main screen will normally display during Filter Cycles or when the spa is in use If...

Страница 14: ...n on any given day SET TIME will still flash in the TIME Menu until the time is actually set but since the spa started at noon the filter cycles will run as programmed Flip Invert Display or Sub Menu...

Страница 15: ...s This unlock sequence can be used from any screen and can be viewed on a locked panel by pressing and holding the Temperature Button or UP button if available Gently press and release the LIGHT butto...

Страница 16: ...d to disable the pumps during service functions like cleaning or replacing the filter Hold Mode will last for 1 hour unless the mode is exited manually Drain Mode Some spas have a special feature that...

Страница 17: ...2 On OFF Start Time and Run Hours and revert to any previous Filter 2 settings Wait to Revert Main Filtration Filter cycles are set using a start time and a duration Start time is indicated by an A or...

Страница 18: ...st Wait to Revert Pour r gler Waiting several seconds will lose any new Lite Timer On OFF Start Time and Run Hours and revert to the previous Lite Timer settings When the Temperature continues to flas...

Страница 19: ...d so it may not appear When it is available set the length of time Pump 1 will run after each use 0 4 hours are available DOL PHIN AD DRES Dolphin II and Dolphin III Applies to RF Dolphin only This me...

Страница 20: ...of hours 0 4 SET SET SET To veiw current setting and to toggle address numbers for Dolphin II or Dolphin III 0 7 SET SET SET to show Address Menu for Dolphin II or Dolphin III To Set To Set To Set To...

Страница 21: ...up Number SIG Configuration Signature Displays the checksum for the system configuration file Heater Voltage Feature not used on CE rated systems Displays the operating voltage configured for the heat...

Страница 22: ...set the device will trip within 7 days See Page 17 A B A B Sensor Temperatures When this is set to On the temperature display will alternate to display temperature from Sensor A and Sensor B in the he...

Страница 23: ...and Sensor B on Main Screen Back to normal operation DIP Switch 1 Test Mode Off 0 or On 1 N A or Special Amperage Rule 1 or 2 120 or 240 VAC input power sensed by a UL system at startup 3 6 or 1 3 He...

Страница 24: ...he GFCI screen The end user must be trained to expect this one time test to occur and how to properly reset the GFCI Warning If freezing conditions exist a GFCI should be reset immediately or spa dama...

Страница 25: ...ain Menu TEMP Range While the Temperature is still flashing press Light repeatedly until UTIL Utilities appears in the LCD Press Light repeatedly until FALT LOG appears in the LCD SET RANGE Main Scree...

Страница 26: ...pa water temp is below 108 F 42 2 C Check for extended pump operation or high ambient temp This message can be reset from the topside panel with any button press M0XX numbers are Message Codes See Pag...

Страница 27: ...hecks below Heater is Dry M027 There is not enough water in the heater to start it The spa is shut down After the problem has been resolved you must press any button to reset and restart heater start...

Страница 28: ...ast 1 hour Call for Service Sensor Failure Sensor A M031 Sensor B M032 A temperature sensor or sensor circuit has failed Call for Service READY RANGE FLTR 1 No Communications The control panel is not...

Страница 29: ...k ON M034 Water may be overheated POWER DOWN THE SPA DO NOT ENTER THE WATER Contact your dealer or service organization Configuration Error Spa will not Start Up Contact your dealer or service organiz...

Страница 30: ...l have a TEST and RESET button on it that allows a user to verify proper function Alternates with temperature or normal display Alternates with temperature or normal display Alternates with temperatur...

Страница 31: ...days Wood skirting and furniture should be cleaned and conditioned per the manufacturers instructions for maximum life Appears on a regular schedule e g every 365 days Filters should be replaced occa...

Страница 32: ...equipment is to be installed in a pit For use only within an enclosure rated CSA Enclosure 3 Connect only to a circuit protected by a Class A ground fault circuit interrupter or residual current devi...

Страница 33: ...se and return it to its position 6 2 Water quality The water in the SPA can be contaminated in many ways Due to warm water and abundant food supplies such as sweat dander skin cream and hair bacteria...

Страница 34: ...on to avoid the water from freezing 3 If the user doesn t want to use it in Winter the water in the spa should be drained away completely then check and make sure there is no water left in the water...

Страница 35: ...Put the cover on for quicker heating Check the heating time is set correctly and the heating temperature It takes 40 minutes for 1000L of water to rise by 1 degree under ideal conditions If the weathe...

Отзывы: