9.11 Statistics
In SMV RMS interface, choose statistics in Function menu to display the frame-drop
information.
SMV Statistics interface
Press Clear to reset all the information to 0 and start the statistics.
Total frame message:
The total received message since start
Dropped frame:
the number of frame-drop
Error sequence:
The SMV counter uncontinuous between two frame messages and the
previous frame number is more than the next frame number.
Repeat: The SMV counter uncontinuous between two frame messages and the previous
frame number is the same as the next frame number.
Repeat:
Out of step:
The SMV synchronization shows 0 indicating the synchronization signal
lost.
Abnormal quality:
The total number of invalid and repair.
Abnormal quality: invalid:
The number of invalid abnormal quality
Abnormal quality: Repair:
The number of repair abnormal quality