![POMCube iCAN Mini 3500 Скачать руководство пользователя страница 24](http://html.mh-extra.com/html/pomcube/ican-mini-3500/ican-mini-3500_user-manual_1578666024.webp)
23
4.4 Parameters of different types of battery
Battery type
Parameters
Sealed
lead-
acid
(SLD)
GEL
lead-
acid
(GEL)
Opened
lead-acid
(FLD)
lithium iron
phosphate
(LFP)
Ternary
lithium
(NCM/NCA)
User define
(User)
Off voltage in over
voltage
60V
60V
62V
60V
60V
36
~
60V
Equalized charge
voltage
58.4V
56.8V
59.2V
-
-
36
~
60V
Improve charging
voltage
57.6V
56.8V
58.4V
56.8V
Adjustable
55.2V
Adjustable
36
~
60V
Adjustable
Floating voltage
55.2V
55.2V
55.2V
56.8V
Adjustable
55.2V
Adjustable
36
~
60V
Adjustable
Alarming voltage
in undervoltage
48V
48V
48V
49.6V
Adjustable
44.8V
Adjustable
36
~
60V
Adjustable
Off voltage in low
voltage
44.4V
44.4V
44.4V
48.8V
Adjustable
43.2V
Adjustable
36
~
60V
Adjustable
Limiting discharge
voltage
42.4V
42.4V
42.4V
44.8V
Adjustable
41.6V
Adjustable
36
~
60V
Adjustable
Delay off time in
over discharge
5s
5s
5s
30s
Adjustable
5s
Adjustable
1
~
30s
Adjustable
Equalizing time
duration
120min
-
120min
-
-
0
~
600min
Adjustable
Equalizing charge
interval
30 days
-
30 days
-
-
0
~
250 days
Adjustable
Improve constant
charge time
120min
120min
120min
120min
Adjustable
120min
Adjustable
10min
~
600min
Adjustable
5. Other functions
5.1 Function of dry contact
Working principle: dry contact can control the switch of diesel generator to charge the battery.
①
Under
normal condition, NC-N contact of this terminal is closed and NO-N contact of this terminal is opened.
②
When the battery voltage reaches low voltage disconnection point, coil of relay is powered, and NO-N is
closed, NC-N is opened, then NO-N contact can drive resistive load 125VAC/1A and 30VDC/1A.