CeramicSteel Sans - Wall Mounted Frameless
Dry Erase Board, Non-Seismic Applications
Safety Requirements
Minimum Required Wall Construction
Drywall with metal studs:
•
Must be atleast 25 ga. (0.018” or .5 mm thick) 33
ksi steel studs 38 mm x 89 mm (1.5” x 3.5”)
•
Studs on maximum 610 mm (24”) centers
•
Must be atleast 16 mm (5/8”) thick Type X
gypsum drywall for the US or 12 mm (1/2”) for EU
•
32 mm (#6 x 1-1/4”) drywall screws on 305 mm
(12”) centers
Verify Wall Construction
CAUTION! Adequate wall construction is
required to support the weight of the board.
Minimum wall construction must be capable
of supporting weight amounts listed in Table
1 on page 6.
Drywall with wooden studs:
•
Stud grade SPF, DF-L or Hem-Fir 38 mm x 89
mm (1.5” x 3.5”)
•
Studs on 610 mm (24”) centers
•
Must be atleast 16 mm (5/8”) thick Type X
gypsum drywall for the US or 12 mm (1/2”) for EU
•
32 mm (#6 x 1-1/4”) drywall screws on 305 mm
(12”) centers
The building’s Engineer of Record must be
consulted to determine if there are any seismic
requirements.