background image

bottom side of the base plate on the OC2-500 control to facilitate heat transfer. 
 
When mounting in the enclosure, select an area that will minimize the possibility 
of metal parts falling between the PC board and OC2-500 base plate, or on the PC 
board and thereby causing shorts. Since the enclosure wall or sub-panel is actually 
used by the OC2-500 as a heat sink, it is necessary that the panel be of sufficient 
size to furnish adequate cooling. If a single OC2-500 is placed in an unventilated 
enclosure with no other heat-generating equipment, a 20”x20” enclosure of 
minimum clearance depth is of adequate size. The top edge of the OC2-500 base 
plate must be located at least 4” below the top surface of the enclosure. If these 
conditions are met, no fans need to be used. 
 
If other equipment which generates significant heat is installed in the cabinet with 
the OC2-500, however, increase enclosure size or add a circulating fan to 
distribute heat within the enclosure. In all cases, though, it can be determined if a 
larger enclosure and/or fan will be needed by measuring the power cube base 
plate temperature. The power cube base plate temperature under all conditions 

cannot exceed 100

°

C

 
4.2 

MOUNTING OF ENCLOSED OC2E-500 CONTROL 

 

The enclosed OC2E-500 control must be mounted in an environment that does not 
exceed 40

°

C. Since this control uses the back of the box for cooling, the control 

must be mounted in a location to permit airflow over the back of the enclosure. It 
is mandatory that the OC2E-500 enclosure back be spaced at least one-half inch 
from any air restricting or thermally non-conductive walls. Spacers are provided 
with the control to permit proper mounting. Refer to Figure 3. 

 
4.3 

WIRING PROCEDURE 

 
Use drawing A1501-100-ES ( Figure 4) on open chassis controls and A1436-000-
WD (figure 3) on enclosed controls for proper external wiring connections. The 
rated RMS current for 5 horsepower control is given in these wiring diagrams. All 
wires which carry armature current are sized the same as those carrying AC line 
current. (This is necessary to account for the form factor of the current being 
supplied to the armature of the motor.) All other wire connections may be # 18 
AWG. 
 
On enclosed controls the AC input connections are made to 3TB. On open chassis 
controls the input connections are made directly to the double fuse holder. For 
open chassis controls, wire connections to terminal strip 1TB on the printed 
circuit board are not to be lugged. 

 

 
 
 

 

Содержание OC2-500

Страница 1: ...Troubleshooting Table II 11 8 2 Troubleshooting Procedure In Case of Fuse Blowing 13 9 POWER MODULES AND D50 TESTING 15 10 MOTOR TESTS 16 11 CONTACTOR OPERATED SYSTEMS OPEN CHASSIS CONTROLS ONLY 16 1...

Страница 2: ......

Страница 3: ...ntrol loops speed and torque that operate simultaneously and independently of each other In most cases the speed loop is in control The speed loop can use either armature voltage or tachometer voltage...

Страница 4: ...is then fed to the IR circuit which permits the achievement of no load to full load regulation of less than 1 of base speed In applications requiring load regulation better than 1 of base speed tacho...

Страница 5: ...al Characteristics Linear Linear Acceleration Time 0 5 to 15 Seconds adjustable Torque Limit of Rated Motor Current Approx 75 to 150 adjustable Maximum Ambient Temperature 40 C External Signal Capabil...

Страница 6: ...late temperature under all conditions cannot exceed 100 C 4 2 MOUNTING OF ENCLOSED OC2E 500 CONTROL The enclosed OC2E 500 control must be mounted in an environment that does not exceed 40 C Since this...

Страница 7: ...rt to the chassis or shorts between terminals Caution should be observed when connecting the motor shunt field Some DC motors are provided with dual field windings which are connectable for high or lo...

Страница 8: ...reverse the A1 and A2 connections to terminals A1 and A2 on 10TB of the OC2 500 control If the motor runs at maximum seed with the potentiometer fully counterclockwise and slows down as the potentiom...

Страница 9: ...nts per Table II and in the order listed in Table II The adjustments are completely independent of each other except as noted below a IR has a slight effect on MIN but MIN does not effect IR b MIN has...

Страница 10: ...ntil ammeter reads rated motor current see nameplate Read motor speed with strobe light or tachometer e If motor speed decreased as motor was loaded adjust the IR trim pot and repeat c and d until lit...

Страница 11: ...w speed e g 10 setting e Apply friction braking to the motor shaft until until motor stalls out CAUTION Watch ammeter to assure that control is limiting current f Stall current should read roughtly 15...

Страница 12: ...r Test Section 8 TROUBLESHOOTING 8 1 TROUBLESHOOTING TABLE The majority of major malfunctions which are normally encountered can be summarized as stated below a Motor does not run b Motor runs only at...

Страница 13: ...PAGE INTENTIONALLY LEFT BLANK 10a...

Страница 14: ...Terminals 10 and 11 on 1TB not connected Either a permanent jumper or contact closure must be used to permit control operation See the external wiring diagrams and contactor operated systems section...

Страница 15: ...wing a Incorrect AC input voltage Check that voltage supplied agrees with the voltage warning label b Incorrect connections between motor and control Recheck all motor connections as given on A1501 10...

Страница 16: ...b does not light move on to step g If the bulb does light turn off the power and remove all connections to 10TB Reapply 230 volts to the control If bulb does not glow trouble is probably a short in th...

Страница 17: ...at zero and turn on all power Light should not burn Increase the speed setting to 20 Lamp brilliance should increase smoothly to nearly full brilliance NOTE Lamp flicker and erratic brilliance may be...

Страница 18: ...ng one lead on the terminal The other lead should be put on the AC terminal With the meter leads on the AC and terminals the Simpson on the RX1 resistance scale the meter should read between 5 15 ohms...

Страница 19: ...s or the field on permanent magnet motors a CEMF will be produced in rotating This will cause the ohmmeter readings to change during rotation Therefore after moving the shaft a small amount stop and c...

Страница 20: ...d to reverse motor rotation This is accomplished by physically reversing the external connections between 10TB terminals A1 and A2 and the A1 and A2 armature lines to the motor In designing a reversin...

Страница 21: ...C voltage sources Basically any DC voltage which is isolated from the AC power lines and which varies from zero to six volts may be applied between 1TB terminals 6 and 5 on 1TB to vary the speed from...

Страница 22: ...terminal 8 in respect to common When the control is supplying 100 of rated motor current there will be approximately a 33mV voltage drop across the current shunt 1MSH In order to accomplish external t...

Страница 23: ...ied c With the control off the jumper connecting pins 1 and 2 on the feedback select 2PL should be changed to connect pins 2 and 3 The jumper can be removed by vertically sliding the jumper off the pl...

Страница 24: ...controlled by Polyspede Therefore only guidelines can be given for checking this item Experience has shown that each application has its own wear rate Removal of the brushes after each three months of...

Страница 25: ...he possible entrance of contaminants into housing e If detailed instructions for assembly and disassembly of a particular unit are required write the speed reducer factory for the information f If you...

Страница 26: ......

Страница 27: ......

Страница 28: ......

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ......

Отзывы: