![Polyaire Zonemaster Unipoint RF Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/polyaire/zonemaster-unipoint-rf/zonemaster-unipoint-rf_owners-manual-and-setup-manual_1575874015.webp)
ZONEMASTER UNIPOINT RF DAMPER CONTROL SYSTEM
- Setup Guide
Page
6b)
Initiating and exiting the setting process
1)
Hold down both and buttons for about
5 seconds until the LCD displays ‘Setting’ on
the top line of the LCD screen.
2)
At the setting mode, pressing button at
any time will return to the normal operation
mode.
6c)
Setting system code
Each system has a default system code of 0 for both the remote
handset and the main control module. This code presents a unique
identification for the system to avoid possible interference (with
neighbours who have installed a similar system) with the effective
range. In case of interference, the code needs to be adjusted to a
different code. There are 8 codes in total (0,1,2,3,4,5,6,7).
Setting system code on remote handset
1)
At the setting mode, select ‘Parameter’ by
pressing button to display its sub-menu.
2)
Use or button to select the System
Code (high lightened).
3)
Use and button to increase or
decrease the code.
Setting system code on main control module
1)
Remove the two side covers on the main
control board, a push button and 8 sets
of LED indicators can be seen.
2)
Press the push button once and the
main control board goes into the setting
up mode. The default setting for system
code is 0.
3)
Press the button again, the system code
changes to 1, and the green LED for
zone 1 lights up as well. This green light
gives the confirmation of the system
code to be 1.
4)
Follow step
3)
to set the system code to the required code.
The required code is confirmed by the number of green
LEDs shown on the board.