background image

IK-E343-001E 

 

 

 

Fig. 1.  DOP-6001 detector with prism reflector 

 

3  

PRINCIPLE OF OPERATION 

 

The  DOP-6001  detector  consists  of  an  infrared  (IR)  light  transmitter  and  a  receiver  located  in  a  single 
enclosure, and an interoperating separate E39-8R prism reflector or 4xE39-8R reflector panel. The detector 
principle  of  operation  consists  in  continuous  analysis  of  optical  air  transparency  in  a  space  between  the 
detector and the reflector (reflector panel).  

The detector can be in one of four modes:   supervision, alarm, fault 

 light beam break, and fault 

 caused 

by  contamination.  If  a  certain,  defined  quantity  of  aerosol  (smoke)  is  found  in  the  air,  reducing  optical 
transparency below a set threshold, then the detector enters an alarm mode. Complete interruption of the 
radiation  beam  (or  its  reflection  due  to  an  object  occurrence  in  its  optical  path)  is  signalled  as  a  fault, 
because  even  the  largest smoke  concentration  in  the  air  does  not  cause  an  entire  break  of  the  detector 
optical path. When the air is clear, the detector is in supervision mode. 

Long  lasting  detector  operation,  especially  in  high  dust  level  premises,  may  lead  to  contamination  (dust 
build-up)  of optical parts of  the detector and the reflector/reflector panel. In order  to maintain constant 
sensitivity  and  fire  detection  ability  during  a  long  time  period,  the  detector  is  equipped  with  automatic 
compensation circuits to monitor its contamination and environ impact conditions. The circuits ensure the 
same sensitivity threshold in the whole compensation range. At a certain contamination level, the detector 
signals a fault mode denoting a necessity to undertake servicing and cleaning works. However, even in this 
mode, the detector is still able to detect smoke and initiate an alarm. A contamination caused fault requires 
cleaning works of the reflector/reflector panel and the detector front surface. After cleaning, the detector 
adjusts to new external conditions and automatically changes its mode from fault to supervision.  

Communication between the  POLON 4000 system control panel and the DOP-6001 detectors is provided 
using a two-wire detection line. A unique, fully digital communication protocol enables transmission of any 
information  from  the  control  panel  to  the  detector  and  vice  versa,  such  as:  surrounding  conditions 
evaluation  (smokiness,  temperature),  their  change  tendency  and  the  current  analogue  value  of 
temperature and smokiness density. 

The DOP-6001 addressable smoke detector is equipped with an internal short circuit isolator, which cuts off 
the efficient detection line from a shorted section, what enables the detector further unfailing operation. 

Analysis function in the DOP-6001 detector is fulfilled by a microprocessor. After the detector optical path 
alignment and initiation the analysis process at the control panel level (detectors in an addressable line), or 
pressing  the  START  push  button  (detectors  in  a  conventional  line),  microprocessor  circuits  analyses  the 

Содержание POLON 4000 DOP-6001

Страница 1: ...IK E343 001E 1 POLON 4000 INTERACTIVE FIRE DETECTION AND ALARM SYSTEM DOP 6001 OPTICAL BEAM SMOKE DETECTOR Installation and maintenance manual IK E343 001E Edition I ...

Страница 2: ...łka z ograniczoną odpowiedzialnością Sp k Glinki 155 Street PL 85 861 Bydgoszcz 11 1438 CPD 0219 PN EN 54 12 DOP 6001 Beam smoke detector operates using absorbed light beam addressable conventional undetachable Application fire security Technical data IK E343 001 manual Read the manual carefully before the detector assembling and commissioning Any nonconformity with the instructions contained in t...

Страница 3: ...s alignment between the detector and the reflector reflector panel The DOP 6001 beam smoke detector is intended for installation in the POLON 4000 system fire detection and alarm control panel lines The detector operates in closed premises at ambient temperatures ranging from 25 o C to 55 o C and relative humidity up to 95 at 40 o C 2 TECHNICAL SPECIFICATIONS Operating voltage in a detection line ...

Страница 4: ... to monitor its contamination and environ impact conditions The circuits ensure the same sensitivity threshold in the whole compensation range At a certain contamination level the detector signals a fault mode denoting a necessity to undertake servicing and cleaning works However even in this mode the detector is still able to detect smoke and initiate an alarm A contamination caused fault require...

Страница 5: ...reflector panel The START push button enables initiation of the detector adjustment process self adjustment and the detector parameters renewed set up after optical parts cleaning works 5 INSTALLATION The DOP 6001 detector interoperates with a reflector panel and then its operating distance ranges from 50 m to 100 m or with an E39 R8 prism reflector at the operating distance between 5 m and 50 m I...

Страница 6: ...lector The mirror should be removed after proper regulation of the optical path between the detector and the reflector The prism reflector position cannot be adjusted and it is recommended to fix it to a flat substrate with screws or glue The detector is properly aligned with the reflector reflector panel when the reflected laser light illuminates the detector In such the situation the external ba...

Страница 7: ... detector testing foil with overprints is included in the service kit During renovation or painting works carried out in the premises where detectors are installed the detector and reflector reflector panel should be taken out Detectors which are damaged in the time of painting and renovation works due to a fault of persons who execute them are not subject to warranty repairs 7 SAFETY CONDITIONS 7...

Страница 8: ...7 m 0 4 m to 1 0 m Over 12 m 7 m 0 6 m to 0 9 m 0 8 m to 1 2 m The maximum area protected by one detector in case the detector reflector panel distance is 100 m for the ceiling height at 10 m amounts to 2D x 100 m ca 1300 m2 so the detector can replace a dozen of spot smoke detectors The distance between the detector IR beam and a side wall of room should not exceed D value and between two adjacen...

Страница 9: ...1E 9 Fig 3 DOP 6001 design and overall dimensions Note Only one detector without an end of line resistor can be installed in a conventional detection line therefore no line output to the next detector is provided ...

Страница 10: ...10 IK E343 001E Fig 4 DOP 6001 detector installation wires connection Fig 5 DOP 6001 detector internal connections and output terminals diagram ...

Страница 11: ... declared in the control panel and all jumpers should be taken out Interoperating line declaration no jumper POLON 4000 system addressable line jumper in ADC1 position TELSAP side line behind ADC1 adapter jumpers in ADC38 and ADC1 position ALFA 3800 side line behind ADC1 adapter jumpers in ADC38 and ADC1 position IGNIS 1000 or CSP 35 system conventional line Fig 6 Jumpers for detector operation de...

Страница 12: ...12 IK E343 001E Fig 8 Reflector panel ...

Страница 13: ...IK E343 001E 13 Fig 9 DOP 6001 detector testing foil with overprints ...

Страница 14: ...14 IK E343 001E Fig 10 Reflector panel assembly IK E343 001E 03 2012 04 2012 ...

Отзывы: