9.
Operation and maintenance
9.1.
Proper use regulations
The reliability of the control panel is subject to appropriate working conditions, supply voltage,
rechargeable batteries state and periodic inspections.
Periodic inspections should be carried out by an authorized technician entrusted with installation
maintenance by the user. Any damage must b immediately reported to the maintenance technician.
When replacing fuses attention should be paid to their nominal values. Do not replace a blown fuse
with a spare one of higher nominal value to avoid device damage.
UCS 6000 control panels are fitted with the following fuses:
Control panel board:
-
F1: 630mA
type: thermal
–
control panel power supply circuit
-
F2: 630mA
type: miniature NANO
2
–
external power supply circuit
-
F3: 3A
type: miniature NANO
2
–
battery charging circuit
Battery (red line):
-
F4: 15A
type: car fuse 19mm 15A
–
blue
9.2.
Periodic inspections and maintenance regulations
Clean battery terminals every half a year.
The batteries charging state should be inspected at least once a year. To do this switch the mains
voltage off for approximately 2 hours, then switch it back on and check whether the rechargeable
batteries cluster will be recharged within 5 hours.
Efficiently operated control panel subject to regular periodic inspections does not require any special
maintenance. It is recommended to periodically clean the outer surface of the panel.