MAINTENANCE OF YOUR WATER HEATER

3 Month Inspection

At least every 3 months, a visual inspection should be 
made of the combustion air inlet as well as the exhaust and 
water piping.  Check the water heater for the following:

• 

Obstructions, damage, or deterioration in the venting 
system. Make sure the exhaust and  combustion air 
supplies are not obstructed. 

• 

Leaking or damaged water and gas piping.

• Presence 

of 

fl ammable or corrosive materials in the 

installation area.

• 

Presence of combustible materials near the water   
heater.

Important:

 Verify proper operation after servicing this water 

heater.

Gas Valve

The gas valve on this water heater has been permanently 
set at the factory for proper operation.  No field adjustments 
are needed and none should be performed.

Removing the Gas Valve

Removal and replacement of the gas regulator valve  
involves the disconnection of gas piping and electrical 
leads. This procedure must be performed by a qualified 
service technician.

Important:  

When removing the gas valve, do not use a 

pipe wrench or vise to grip the body. Do not apply any force 
to the gas valve or the cast flange fitting on the inlet side 
of the gas valve (see figure 25.) Such force may break or 
crack these components.

1.  Turn temperature dial counterclockwise to the lowest    

setting and turn off electrical power to appliance.

2.  Shut off the gas at the manual shut-off valve on the    

gas supply line. See figure 19 for reference.  Remove    
the access door.

3.  Disconnect the gas piping connection just outside   

the base of the water heater .  Note:  Use a second 
pipe wrench on the gas piping inside the skirt to avoid 
cracking the gas valve or the flange fitting.   

4.  Remove the pressure tap from the gas valve (see     

figure 25).  The hose should not be disconnected.

5.  Remove the Phillips head screw holding the electrical    

plug and remove electrical plug from the gas valve.

6.  Remove the three T-25 Torx head brass screws that  
 

attach the gas valve to the venturi manifold, using   
the T-25 Torx wrench supplied with the gas valve kit 

(model VK8115V, part number 6903775.)

7.  Remove the gas valve from the unit keeping the     

rubber gasket with the gas valve .

8.  Remove the flange from the gas inlet side  of the valve 

by removing the four (4) attachment  screws.

Figure 25

Replacing the Gas Valve

Important

:  The rubber gasket that seals the gas valve to 

the venturi manifold must be used (previous gaskets may 
be reused, if in good condition).  Make sure the gasket is 
properly inserted into the recess on the gas valve prior to 
installation (see figure 25 for exact placement of the rubber 
gasket).  

1.  Remove the O-ring from the flange (removed from the 

old gas valve) and replace it with the one provided 
in the gas valve kit (model VK8115V, part number 
6903775.)

2.  Reattach the elbow flange to the gas valve.  Tighten  all 

four screws securely.

3.  Place the three T-25 Torx screws through the proper     

holes in the venturi manifold flange.  See figure 25.

4.  Properly install a new rubber gasket (provided) as       

shown in figure 25.

5.  Position the gas valve and start all three screws 

(projecting downward from the venturi manifold) into  
the gas valve.  A T-25 Torx wrench has been provided  
in the gas valve replacement kit (model VK8115V, part 
number 6903775.)

Note: 

All three T-25 Torx screws must be properly tightened 

to secure the seal between the gas valve and the venturi 
manifold. 

6.  Reconnect the pressure tap to the port on the new gas  

valve (see figure 25).

7.  Reconnect the external gas supply line to the gas pip-

ing  on the gas valve. Be sure to use approved Teflon 
tape or pipe joint compound suitable for gas piping.

Note:  

Use a second pipe wrench on the gas piping inside 

the skirt to avoid cracking the gas valve or the cast fitting.

8.  Reconnect the electrical plug to the gas valve and       

secure it with the screw provided.

9.  Turn gas supply on and check for leaks. Use a chlo-

ride-free soap and water solution (bubbles forming 
indicate a leak) or other approved method. All leaks 
must be fixed immediately.

10.  Be sure tank is completely filled with water before re-

storing power to the water heater. Follow operating      
instructions on Page 25.

11.  Ensure proper operation of the water heater, then rein-

stall the access door.

If additional information is required, contact the Product 
Service and Support Group at 1-800-456-9805.

Содержание PG10* 100-199-3NV

Страница 1: ...have the following information ready 1 Model number 2 7 Digit product number 3 Serial number 4 Date of installation 5 Place of Purchase Table of Contents 2 Do not store or use gasoline or other flamm...

Страница 2: ...mend the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appliance which is connected to the hot water system If hydrogen is present there will probably...

Страница 3: ...ples of qualified service technicians include those trained in the plumbing and heating industry local gas utility personnel or an authorized service person The manufacturer and seller of this water h...

Страница 4: ...ce Maintain proper clearances as specified on the data plate Figure 1 Garage Installation Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other applia...

Страница 5: ...sembly should be glued to the exhaust pipe see figure 3C Note The trap should be aligned so that the exhaust pipe is in a vertical position close to the surface of the water heater Figure 2 Minimum Cl...

Страница 6: ...ctions can be found in this manual in state or local codes or the authority having jurisdiction or in the absence of such the National Fuel Gas Code ANSI Z223 1 NFPA 54 Latest Edition Canadian install...

Страница 7: ...ipe 4 Concentric Vent Through the Wall 5 Concentric Vent Through the Roof All pipe fittings pipe cement primers and procedures must conform to American National Standard Institute and American Society...

Страница 8: ...op and side of window or door that may be opened Do not install below a window or door that may be opened C Clearance to permanently closed window D 12 in 30 cm min vertical clearance to ventilated so...

Страница 9: ...the water heater as possible This is to drain any water that may be in the combustion air pipe and prevent it from entering the blower Connect the trap drain line to a suitable drain or downstream of...

Страница 10: ...gure 9A for the proper location of the air inlet with respect to the exhaust outlet termination The vertical exhaust outlet termination is a 2 inch pipe which terminates at least 12 inches above the i...

Страница 11: ...ures 10A 13Abelow for vent terminal specifications Note For replacement installations previously installed American Water Heater Company supplied concentric vent kits are acceptable for use on 100 000...

Страница 12: ...d inward Install a drain tee assembly and trap in the inlet vent as close to the water heater as possible This is to drain any water that may be in the combustion air pipe and prevent it from entering...

Страница 13: ...for the proper location of the air inlet with respect to the exhaust outlet termination The vertical exhaust outlet termination is a 3 inch pipe which terminates at least 12 inches above the inlet ai...

Страница 14: ...for vent terminal specifications Figure 11B Through the Wall Termination Figure 12B Through the Roof Termination Figure 13B Concentric Vent Piping Installation Note For concentric venting terminations...

Страница 15: ...in along the top side of the nipple 34 50 gal models only Connect the hot water supply 50 gal and below use 1 NPT 100 gal use 1 1 2 NPT to the fitting marked HOT OUTLET 2 Always use a suitable grade o...

Страница 16: ...ng which will contaminate the potable water supply Closed System Thermal Expansion When a backflow prevention device or check valve is installed it can create a Closed System Heating water in a closed...

Страница 17: ...empering valve or supply line to the heating system to remove air bubbles from the system Do not connect the water heater to any system or components previously used with non potable water heating app...

Страница 18: ...ter than or equal to the input rating of the water heater The Discharge Line Must not be smaller than the pipe size of the relief valve or have any reducing coupling installed in the discharge line Mu...

Страница 19: ...ence figure 19 for gas piping installation 1 Install a readily accessible manual shut off valve in the gas supply line as recommended by the local utility Know the location of this valve and how to tu...

Страница 20: ...Nationally listed recognized fuel gas and carbon monoxide CO detectors are recommended in all applications and should be installed using the manufacturer s instructions and local codes rules or regula...

Страница 21: ...ervice box 2 Loosen the screws securing the access panel to the electrical compartment The electrical wiring diagram for 34 50 gal models can be found on the inside of the access panel at the base of...

Страница 22: ...ND GND GND FUSED DISCONNECT L1 NEUTRAL GND PSI PSO PRESSURE SWITCH BLACK WHITE WHITE RED LED YELLOW LED GREEN LED BROWN YELLOW RED THERMOSTAT DIAL ORANGE GAS VALVE BROWN BLUE BLUE WHITE IGNITER RED GR...

Страница 23: ...ds the heater at 1 8 per foot Away from corners other vents windows etc Alternate Horizontal Correct relationship outlet to inlet 12 Min above anticipated snow level 2 exhaust outlet air inlet pipe sl...

Страница 24: ...calling for heat which signals the beginning of the ignition sequence see figure 21 and Red Ignition control is signaling the gas valve to open Figure 21 Sequence of Operation When the thermostat call...

Страница 25: ...systems used with this water heater are designed for temperatures higher than 130 F Refer to the manufacturer s instruction manuals supplied with this type of equipment for recommended temperature se...

Страница 26: ...nnect a hose to the drain valve and terminate it to an adequate drain Note The drain hose should be rated for at least 200 F If the drain hose does not have this rating open the cold water inlet valve...

Страница 27: ...umber 6903775 7 Remove the gas valve from the unit keeping the rubber gasket with the gas valve 8 Remove the flange from the gas inlet side of the valve by removing the four 4 attachment screws Figure...

Страница 28: ...y Detection SC SL Soft Lockout Control Automatically resets after 60 minutes SL3 Soft Lockout Hard Lockout Control automatically resets after 60 minutes with a maximum of 3 resets followed by hard loc...

Страница 29: ...OFTWARE OPERATION SEQUENCE IGNITION CONTROL MODULE SOFTWARE OPERATION SEQUENCE For 175 000 BTU Hr models and above the flame establishing period is six seconds For the first 3 seconds the gas valve is...

Страница 30: ...34 DRAIN VALVE 35 POTENTIOMETER 36 VENTURI GASKET not pictured 37 BLOWER ISOLATION RELAY 150 000 BTU Hr TOOLS REQUIRED FOR SERVICING TOOL FUNCTION VOLT OHMMETER MEASURE VOLTAGE RESISTANCE CLAMP ONAMM...

Страница 31: ...34 DRAIN VALVE 35 TEMPERATURE AND PRESSURE RELIEF VALVE TOOLS REQUIRED FOR SERVICING TOOL FUNCTION VOLT OHMMETER MEASURE VOLTAGE RESISTANCE CLAMP ONAMMETER MEASURE CURRENT STOPWATCH CLOCK GAS CONSUMPT...

Страница 32: ...3 48 1 2 22 15 3 4 40 1 2 41 6 3 8 5 1 2 6 5 8 150 PG10 50 130 2NV OR 2PV 50 130 2 OR 3 62 3 8 22 15 3 4 54 1 2 55 6 3 8 5 1 2 6 5 8 176 PG10 34 150 2NV OR 2PV 34 150 2 OR 3 48 1 2 22 15 3 4 40 1 2 4...

Отзывы: