THROUGH THE WALL UNIT
20
PTTW CONTROL SPECIFICATIONS
1. ABBREVIATIONS
ST
= Setting temperature
RT
= Room air temperature
IPT
= Indoor coil temperature
OPT
= Outdoor coil temperature
RAS = Room air sensor
PTC data = R25-5.00KOhm±1% B25/50=3470K±1%
2. CONTROL SYSTEM OPERATION
2.1. REMOTE HANDSET AND ON-BOARD PANEL OPERATION
2.1.1. REMOTE HANDSET FUNCTIONS
Remote handset functions are Unit ON/OFF, Mode, Fan Speed, Set Temperature, Swing
Function, Timer ON, Timer OFF, Electric heater ON/OFF and Sleep Function.
2.1.2. ON-BOARD PANEL FUNCTIONS
On-board panel functions are Unit ON/OFF, Mode, Fan Speed, Set Temperature and Electric
heater ON/OFF.
2.2. MODE INTRODUCTION
2.2.1 AUTO MODE
After turning the unit on, select the auto mode. The unit will select its operation mode by
judging room temperature (see below table):
Indoor temp.
Indoor
68°F
68°F
І
indoor
І
77°F
Indoor
77°F
Operating mode
HEATING
FAN
COOLING
Standard fixed setting
temperature
68°F
71.6°F
77°F
2.2.2 COOLING MODE
2.1.2.1 Setting temperature: 64.4°F -86°F.
2.1.2.2 Working conditions of compressor:
Содержание PTTW-10-EC+EH Series
Страница 1: ...ENGINEERING MANUAL PTTW 10 EC EH SERIES THROUGH THE WALL HEAT PUMPS 2010 ARI V 1 5...
Страница 8: ...THROUGH THE WALL UNIT 7 NOISE LEVEL INDOOR FAN MODE...
Страница 9: ...THROUGH THE WALL UNIT 8 NOISE LEVEL INDOOR COOLING MODE...
Страница 10: ...THROUGH THE WALL UNIT 9 NOISE LEVEL OUTDOOR COOLING MODE...
Страница 13: ...THROUGH THE WALL UNIT 12 EXPLODED DRAWING...
Страница 17: ...THROUGH THE WALL UNIT 16 ELECTRIC WIRING DIAGRAM For PTTW 10 EC EH...
Страница 28: ...THROUGH THE WALL UNIT 27...
Страница 33: ...THROUGH THE WALL UNIT 32 THIS IS THE END...