Interconnecting Wiring
It is recommended using screened cable in electrically noisy areas.
Do not install fan coil unit in a location where electromagnetic waves may be directly emitted towards infra-red
receiver on the unit.
Install the unit and components as far away as is practical (at least 5m) from any electromagnetic wave source.
Use shielded sensor cable in where electromagnetic waves exist.
Install a noise filter if necessary.
Wiring Procedures
1.
Open the terminal block cover by removing the 4 screws. (Figure B.13.1)
2.
Connect power cable to the terminal according to the wiring diagram.
3.
Connect room temperature sensor and coil temperature sensors to the control box.
4.
Connect receiver display.
5.
Connect wall pad (optional).
6.
Slide the control box into the unit casing. (Figure B.13.2)
Figure B.13.1
Figure B.13.2
NOTES
Please ensure the cable of the main power supply is longer than 500mm from control box terminal block.
This is to ensure the control box can be slid out easily during maintenance activities.
Always take safety precautions before wiring for main supply. See section B.1, Safety Precautions.