SK2018 CHV2-V/P-ECM-001
Operating Limits
Power supplies
Volt
Phase
Hz
230
1
50
220
1
60
Water circuit
Minimum entering water temperature
+2 °C
Maximum entering water temperature
+80 °C
Water side recommended maximum pressure
1600 kPa
Before Installation
The installation site must be established by the system designer or other qualified professional, taking account of the
technical requisites and current standards and regulations.
Coanda fan coil units must be installed by qualified personnel only.
Coanda fan coil units are designed for horizontal installation in a ceiling, for intake of fresh air from outside and for
diverting a small part of the treated air into a neighboring room.
They must be installed in such a way as to enable treated air to circulate throughout the room and allow the minimum
distances required for technical maintenance operations.
It is advisable to place the unit close to the installation site without removing it from packaging.
Do not put heavy tools or weights on packaging.
Upon receipt, the unit and the packaging must be checked for damage sustained in transit and if necessary, a damage
claim must be filed with the shipping company.
Check immediately for installation accessories inside the packaging.
Do not lift unit by the condensate drain discharge pipe or by the water connections or front panel; lift the unit using
four mounting brackets. (Figure B.4.1)
Check and note the unit serial number.
Figure B.4.1
Brackets