ALARM PARAMETER SETTING.
Press ALARM (key lamp flashes):
This messagge will be displayed instead of the
°Set Minimum Alarm temperature value
.
Press + or - to modify, press ALARM to confirm.
At this point: this messagge will be displayed instead of the
°Set Maximum Alarm temperature value
.
Press + or - to modify, press ALARM to exit.
COSt PROGRAMMING
(System constants)
These settings refer to the mode of operation of the system and must be made
on initial start-up. Press - / + / HEAT together at least one second:
the message
C.O.S.t.
will be displayed.
The COST messagge are displayed in sequence if you press + to go forward
or - to go back.
When you reach the messagge required (see table below) press + or - to set a
new value and then ALARM to confirm.
The next system constant will then appear.
You can press HEAT to escape and return to the
Run Mode
.
*4) Different mode of ventilator initial start-up optionally settable useful for speed
*1) For more details see
Operative Diagrams
*5)
tEnP =1
; °C Temperature range.
tEnP =2
; °F Temperature range.
*6) You can correct the readings on the sensor (+ or -).
regulation (step from 0 to 1 speed).
tYPE= 1
: 0 to 1 step become in normal mode.
tYPE= 2
: 0 to 1 step become with a momentary 10 seconds at speed 2.
tYPE= 3
: 0 to 1 step become with a momentary 5 seconds at speed 3.
tYPE= 4
: 0 to 1 step become with a momentary 5 seconds at speed 4.
*2)
tinE= 1
:
t.on
-
t.oF
setting mode (see VENT key) in seconds.
tinE= 2
:
t.on
-
t.oF
setting mode (see VENT key) in minutes.
Mess.
Valore
Significato
Note
r.1
0.0°
°C VENT.1 start setting referring to
vEnt
set.
*1)
r.2
1.0°
°C VENT.2 start setting referring to VENT 1 start.
*1)
r.3
1.0°
°C VENT.3 start setting referring to VENT 2 start.
*1)
r.4
1.0°
°C VENT.4 start setting referring to VENT 3 start.
*1)
r.5
1.0°
°C VENT.5 start setting referring to VENT 4 start.
*1)
r.6
1.0°
°C VENT.6 start setting referring to VENT 5 start.
*1)
d.vEn
0.2°
°C Ventilation differential
*1)
S.vEn
0"
Ventilation step on dalay seconds
d.HEA
0.2°
°C Heat differential
*1)
d.COL
0.2°
°C Cool differential
*1)
tinE
= 1
t.on
-
t.oF
setting mode (=1 seconds, =2 minutes)
*2)
StEP
= 1
Ventilation setting mode.
*3)
tYPE
= 1
Start Ventilation actioning mode
*4)
tEnP
= 1
Temperature representation (=1 °C, =2 °F)
*5)
Ad.tE
0.0° °C input sensor temperature correction (+ or -)
*6)
*3)
StEP= 1
:
Ventilation in speed regulation mode.
StEP= 2
: Ventilation in on-off mode (progression regulator)*.
* To obtain this type of functioning, the 41-42 terminals has to be connected.
Press + :
will be displayed followed by
°Maximum Temperature Recording.
Press - :
will be displayed followed by
°Minimum Temperature Recording.
VIEWING TEMPERATURE RECORDING
Values recorder are memory permanent stored: for memory clear keep pushed + keys
for more than 3 seconds:
CLEA
messagge will be composed on display before clearing operation.