ALARM PARAMETER SETTING.

Press ALARM (key lamp flashes):
This messagge will be displayed instead of the

°Set Minimum Alarm temperature value

.

Press or to modify, press ALARM to confirm.

At this point: this messagge will be displayed instead of the

°Set Maximum Alarm temperature value

.

Press or to modify, press ALARM to exit.

COSt PROGRAMMING

 

(System constants)

These settings refer  to the mode of operation of the  system and must be made
on initial start-up. Press  - / + / HEAT together at least one second:
the message 

C.O.S.t.

    will be displayed.

The COST messagge are displayed in sequence if you press  +  to go forward
or  -  to go back.
When you reach the messagge required (see table below) press + or - to set a
new value and then ALARM to confirm.
The next system constant will then appear.
You can press HEAT to escape and return to the 

Run Mode

.

*4) Different mode of ventilator initial start-up optionally settable  useful for speed

*1) For more details see 

Operative Diagrams

*5)

 tEnP =1

 ; °C  Temperature range.

tEnP =2

 ;  °F  Temperature range.

*6) You can correct the readings on the sensor (or -).

regulation (step from 0 to speed).

tYPE= 1

  :  0 to 1 step become in normal mode.

tYPE= 2 

 :  0 to 1 step become with a momentary 10  seconds at speed 2.

tYPE= 3 

 :  0 to 1 step become with a momentary   5  seconds at speed 3.

tYPE= 4 

 :  0 to 1 step become with a momentary   5  seconds at speed 4.

*2)  

tinE= 1

  : 

 t.on

 - 

t.oF

 setting mode (see VENT key) in seconds.

tinE= 2 

 :  

t.on

 - 

t.oF

 setting mode (see VENT key) in minutes.

Mess.

Valore

Significato

Note

r.1

0.0°

 °C VENT.1 start setting referring to 

vEnt

 set.

*1)

r.2

1.0°

 °C VENT.2 start setting referring to VENT 1 start.

*1)

r.3

1.0°

 °C VENT.3 start setting referring to VENT 2 start.

*1)

r.4

1.0°

 °C VENT.4 start setting referring to VENT 3 start.

*1)

r.5

1.0°

 °C VENT.5 start setting referring to VENT 4 start.

*1)

r.6

1.0°

 °C VENT.6 start setting referring to VENT 5 start.

*1)

d.vEn

0.2°

 °C Ventilation differential

*1)

S.vEn

0"

 Ventilation step on dalay seconds

d.HEA

0.2°

 °C Heat differential

*1)

d.COL

0.2°

 °C Cool differential

*1)

tinE

= 1

 t.on

 -

 t.oF 

setting mode (=1 seconds, =2 minutes)

*2)

StEP

= 1

 

Ventilation setting mode.

*3)

tYPE

= 1

 Start Ventilation actioning mode

*4)

tEnP

= 1

 Temperature representation (=1 °C,  =2 °F)

*5)

Ad.tE

 0.0°  °C input sensor temperature correction (+ or -)

*6)

*3)  

StEP= 1

  : 

 

Ventilation in speed regulation mode.

StEP= 2 

 :  Ventilation in on-off mode (progression regulator)*.

*  To obtain this type of functioning, the 41-42 terminals has to be connected.

Press  +  :

will be displayed followed by

°Maximum Temperature Recording.

Press  -  :

will be displayed followed by

°Minimum Temperature Recording.

VIEWING TEMPERATURE RECORDING

Values recorder are memory permanent stored: for memory clear keep pushed  +  keys
for more than 3 seconds:

CLEA

  messagge will be composed on display before clearing operation.