background image

10

Pub. No. OM-A-75 REV. 4 — March 2006

MAINTENANCE

AIR DRYER MAINTENANCE

The dryer is factory tested before shipping. All controls are 
calibrated for automatic operation. If the dryer is installed 
in clean surroundings, within the temperature limits of the 
specified ambient, the dryer will run trouble-free for a very 
long time. Routine maintenance procedures recommended 
are the following:

1.

Checking the fan motor(s) for proper operation to 
maintain the cooling air to be drawn through the 
condenser and blown over the refrigerant 
compressor. If the dryer is equipped with condenser 
ambient filters, check, clean or replace as needed to 
maintain the proper air flow through the condenser.

Dirty ambient filters will reduce the air flow through 
the condenser, and trip the compressor “off” at the 
overload control.

2.

For dryers without ambient filters, clean the 
condenser periodically to maintain the proper heat 
transfer on the condenser coil. Dirty condenser will 
raise the head pressure of the refrigeration system 
and trip the compressor “off” at the overload control.

Running the compressor on high head pressures may 
cause premature failures. Check the ambient 
temperature limits to be maintained at the 
installation.

3.

Check and clean water-cooled condensers for dirt, 
scale and sludge buildup every year or as needed. 
Cooling tower water condensers may need cleaning 
more often if the water is not properly treated.

4.

Check the suction pressure gauge. Reading should 
be within the specified range after a few minutes of 
start-up. Suction pressure below the range will cause 
freeze-up inside the air system, increasing the 
pressure drop across the air dryer. Suction pressure 
above the range will reduce the refrigeration cooling 
capacity.

5.

Check the pressure drop across the air dryer at full 
capacity flow. If it is higher than specified value 
(normally 5 PSI or less), consult factory. If pressure 
drop increases over years of operation, it may be 
due to particulate buildup from air compressor 
intake. In that event, back-flush the dryer with any 

MILD DETERGENT

. See Figure 2.

To back-flush, disconnect air dryer, plug the drain line and 
fill the air system with the detergent water solution. Hold it 
for 4-6 hours. Circulate the detergent from air outlet to air 
inlet with a pump. Flush the system with warm water. If 
pressure-drop still exists, contact factory.

FIGURE 2 — BACK FLUSH FLOW DIAGRAM

AUTOMATIC DRAINS

The recommended settings for the drain time is determined 
by the moisture load. The cycle time should be adjusted to 
approximately 3 to 4 minutes. The drain time should be set 
so the drain expels all of the liquid and then a short burst 
of air.

Periodically check the automatic drains for proper 
drainage. If the drains are not functioning, the condensed 
moisture will be re-entrained downstream of the air dryer. 
Float operated automatic drains need periodic cleaning 
with soap and water to remove solids from the valve seat. 
If the valve is stuck open, clean with soap and water and 
then use compressed air to clean the valve seat. Electronic 
solenoid operated drains may be manually tested 
periodically for proper operation. 

AIR OUTLET

AIR INLET

A/A HEAT EXCHANGER

A/R HEAT EXCHANGER

SEPARATOR

MILD DETERGENT

CIRCULATING
PUMP

PLUG

Содержание AD-1500

Страница 1: ...Printed in U S A Publication No OM A 75 March 2006 Rev 4 Owner s Manual NON CYCLING REFRIGERATED AIR GAS DRYER ...

Страница 2: ... Doing this will extend the warranty to 24 months from date of shipment from Company s factory See back page for actual Warranty details DATE OF PURCHASE MODEL SERIAL NO Record above information from nameplate Retain this information for future reference Replacement Price 25 00 ...

Страница 3: ...art Up and Operation 6 Design Conditions 6 Start Up Procedure 6 Operating Range and Control Settings 7 Digital Dry Guard DDG Controller Operation 7 Shutdown Procedure 9 Operating Conditions 9 Maintenance 10 Air Dryer Maintenance 10 Automatic Drains 10 Compressor 12 Expansion Valve 12 Hot Gas Bypass Valve 12 Refrigerated Air Dryer Service CheckList 14 Troubleshooting 15 ...

Страница 4: ...aged in any manner Notify authorized service facility for examination repair or other adjustments 3 USE SUITABLE PARTS ACCESSORIES Do not use air pressurized accessories or parts in the air system not suitable for the maximum air pressure 4 RELEASE AIR PRESSURE SLOWLY Fast moving air will stir up dust and debris which may be harmful Release air pressure slowly when depressurizing your system to av...

Страница 5: ...URE GAUGE REMOVES 66 MOISTURE AIR COOLED AFTERCOOLER 2 P RECEIVER T C PREFILTER REGENERATIVE AIR DRYER PARTICULATE AFTERFILTER 4 5 TO PLANT USE 37 F RECEIVER REFRIGERATED COALESCING AFTERFILTER DRAIN R OPTIONAL 3 VALVE SYSTEM BYPASS P 6 P CONTROL OPTIONAL AUTO DRAIN 1 SEE PNEUMATECH BULLETIN PWC 1 2 SEE PNEUMATECH BULLETIN A 3 3 SEE PNEUMATECH BULLETIN A 16 4 SEE PNEUMATECH BULLETIN A 8 5 SEE PNEU...

Страница 6: ...pressed air to the air dryer which will cause premature failures Aftercoolers must be followed by a separator and an automatic drain to remove the condensed moisture before the compressed air reaches the air dryer If the condensed water is not removed at the aftercooler separator drain it will reduce the cooling capacity of the air dryer Aftercoolers will condense approximately 2 1 2 to 3 times mo...

Страница 7: ... to the dryer must meet the national NEC and local code requirements Check the voltage specified on the nameplate to the electrical power connecting to the dryer Electrical connections must be made by an electrician SCROLL COMPRESSOR Air dryers with a scroll compressor are uni directional and to function properly they must be phased correctly To turn the com pressor clockwise use a phase sequence ...

Страница 8: ...tart up Power to the air dryer can be left on to energize the crankcase heater for the off cycle during evening or weekend shutdowns 3 Check the temperature on the crankcase of the compressor to make sure the crankcase heater is working before starting the dryer 4 For water cooled Air Dryers ADW make sure the water supply Minimum Pressure 35 PSIG is available at the condenser inlet The water regul...

Страница 9: ...G R 22 air cooled units with fan cycling 190 to 210 PSIG R 22 water cooled units 3 Refrigerant Discharge Pressure R 134a 75 to 170 PSIG R 134a air cooled units 115 to 135 PSIG R 134a water cooled units 4 Refrigerant Low Pressure Switch CUT OUT 20 PSIG R 134a CUT IN 40 PSIG R 134a CUT OUT 45 PSIG R 22 CUT IN 70 PSIG R 22 5 Refrigerant High Pressure Switch 250 PSIG R 134a air cooled units 405 PSIG R...

Страница 10: ...on for different drain types The mode of operation for timed drains i e 4477 A B or C models is described below as item A The mode of operation for fully automatic float operated drains i e model 4488 is described as item B For all modes the DRAINS POWER ON LED indicates that the drain is receiving power Pushing the DRAIN TEST key will send power to the drain if it is not already receiving power A...

Страница 11: ...on the dryer bypass piping At this time the dryer is isolated and can be depressurized ready for servicing 3 Turn the power switch to the OFF position NOTE The alarm indication light red signifies the refrigerant compressor is not running The reasons can be Low suction pressure High discharge pressure Electrical problems Loss of refrigerant Dirty condenser Leaking evaporator etc Refer to Troublesh...

Страница 12: ...f start up Suction pressure below the range will cause freeze up inside the air system increasing the pressure drop across the air dryer Suction pressure above the range will reduce the refrigeration cooling capacity 5 Check the pressure drop across the air dryer at full capacity flow If it is higher than specified value normally 5 PSI or less consult factory If pressure drop increases over years ...

Страница 13: ...il J Install the drain valve in the system FIGURE 3 DRAIN VALVE Recommended Operation and Maintenance for the Particle Strainer The particle strainer should be cleaned once every week or as needed 1 Close the shut off valve on the particle strainer 2 Depressurize the drain by pressing the drain PRESS TO TEST or DRAIN TEST key 3 Unscrew bottom of the particle strainer and clean the screen FIGURE 4 ...

Страница 14: ... adjustments are needed only at the time of valve replacement Expansion valve service must be performed by a qualified refrigeration technician HOT GAS BYPASS VALVE Model AD 10 and larger air dryers come equipped with modulating hot gas bypass valves This valve maintains the refrigerant suction pressure in varying load conditions The dryer will run from no load to full load conditions without free...

Страница 15: ...Pub No OM A 75 REV 4 March 2006 13 FIGURE 6 FLOW DIAGRAM ...

Страница 16: ... _______________________________________________________________________________ 6 Air in pressure PSIG _________________________________________________________________________________ 7 Air out pressure PSIG ________________________________________________________________________________ 8 Refrigerant suction pressure when unit is operating PSIG __________________________________________________...

Страница 17: ...d 4 Safety controls open 5 Air switch open Dead end control 6 Frozen locked compressor 7 Wiring improper or loose 1 Close disconnect switch to start 2 Replace fuse 3 Turn switch off wait 15 minutes check for overload condition 4 Repair or replace 5 Check air pressure Adjust air and or switch If defective repair or replace 6 Repair or replace 7 Check wiring against diagram B Unit short cycles 1 Mot...

Страница 18: ...er 4 Location too hot 5 Defective condenser pressure switch 6 Defective fan motor 7 Fan operating in wrong direction 8 Defective water regulating valve 1 Purge or vacuum and recharge 2 Check for reason repair 3 Blow clean with compressed air 4 Cool ambient relocate unit add ventilation 5 Repair or replace 6 Replace 7 Switch two wires at disconnect 8 Adjust repair or replace H Head pressure too low...

Страница 19: ...System pressure low 2 Precooler and or evaporator clogged 3 Incorrect piping 4 Air overload 5 Unit too small 6 Excess water in unit 7 Evaporator freeze up 8 Clogged air compressor intake filter 9 Dirty air system 1 Increase pressure 2 Back flush using mild detergent Figure 2 on Page 10 3 Increase line size and or correct piping as required 4 Reduce overload 5 Add another unit or replace with large...

Страница 20: ...nd valves on Intermediate Controls for defects in material or workmanship covering Components only provided a Customer notified the Company of any claim of defect in material or workmanship within sixty 60 months from date of shipment from the Company s factory b Customer holds the Product or Component for inspection by the Company s representative c Customer returns the Component s only with Comp...

Отзывы: