Function block protocol
9499 040 50511
40
Output variable
Output variable processing(function no.: 4)
Code
Descr. R/W Type Description
Range
Rem.
B2
41 Y
min
R/W FP
Min. output limiting
-105..105 %
42 Y
max
R/W FP
Max. output limiting
-105..105 %
43 Y0
R/W FP
Working point f. output variable
-105..105 %
44 Yh
R/W FP
Max. mean value of output
5..100%
45 LYh
R/W FP
Limit for mean value formation
0,1 .. 10,0
Tuning
Self-tuning(function no.: 5)
Code
Descr. R/W Type Description
Range
Rem.
B2
41 YOptm R/W FP
Output variable during process at rest
-105..105
42 dYopt
R/W FP
Step height during identification
5..100
43 POpt
R/W INT
Parameter set to be optimized
0...1
44 OXsd
R/W FP
Hysteresis with parameter switch-over
0.0..9999
45 Trig1
R/W FP
Trigger point 1
0.0..9999
Paramset x
Control parameter set 1 / 2(function no.: 6,7)
Code
Descr. R/W
Type Description
Range
Rem.
B2
41 Xp1
R/W
FP
Proportional band 1
0.1..999.9
42 Tn1
R/W
FP
Integral time 1
0..9999
43 Tv1
R/W
FP
Derivative time 1
0..9999
44 T1
R/W
FP
Min. cycle time 1
0.4..999.9
45 Xp2
R/W
FP
Proportional band 2
0.1..999.9
46 Tn2
R/W
FP
Integral time 2
0..9999
47 Tv2
R/W
FP
Derivative time 2
0..9999
48 T2
R/W
FP
Min. cycle time 2
0.4..999.9
Start-up circuit
(function no.: 10)
Code
Descr. R/W Type
Description
Range
Rem.
B2
41 Ya
R/W FP
Maximum output value
5 .. 100 %
42 Wa
R/W FP
Start-up set-point
-999 .. 9999
43 TPa
R/W FP
Start-up holding time
0 .. 9999 min