130519/A ControlPro | Short user manual
EN - 30
There are two ways to suppress an ALARM alert (including the buzzer):
1. Push the SUPPRESS button on the HMI
2.
Push and hold the black button (FILTER CLEANING) on the Panel for 5 seconds
In case of an ALARM alert:
• Suppress the WARNING alert + buzzer.
• Solve the problem that is displayed on the screen.
• Push the RESET button.
If you are unable to solve the problem immediately, you can temporarily suppress the
ALARM alert. The ALARM screen will be minimized, but the red ALARM button remains
visibile on the Homescreen.
• Select the ALARM button on the Homescreen to show the alarm details again and
proceed as written above.
7.2.1 Alarm codes
A
B
C
D
E
F
Code
Alarm
Action
Reset
A
uto / Manual
Alarm LED
Buzzer
A101
Fan Alarm
Repair possible fan defects.
M
√
√
A102
Fan Alarm
- Danfoss
frequency inverter
Frequency inverter alarm. Consult
the Manufacturer’s manual for more
detailed information on the specific
alarm code.
M
√
√
A103
Fan Alarm
- Danfoss
frequency
inverter- Trip
Locked
Trip lock frequency inverter alarm.
To reset this alarm, switch off the
power supply of the frequency
inverter. Consult the Manufacturer’s
manual for more detailed
information on the specific alarm
code.
M
√
√
A105
FIRE ALARM
- EMERGENCY -
M
√
√
A106
Sliding valve not
opened alarm
Sliding valve is not (fully) opened.
Repair or replace sliding valve.
M
√
√
A
B
C
D
E
F
Code
Alarm
Action
Reset
A
uto / Manual
Alarm LED
Buzzer
A107
Sliding valve not
closed alarm
Sliding valve is not (fully) closed.
Increased risk of fire. Repair or
replace sliding valve.
M
√
√
A108
External alarm
signal
M
√
√
A109
Compressed air
No compressed air. The filter
cleaning system does not function.
Reconnect to compressed air
supply.
M
√
√
A110
Communication
frequency inverter
Frequency inverter communication
fault. Check the cable and
connections and repair/replace if
necessary.
M
√
√
A111
Fan Alarm – VFD
Danfoss – Manual
Mode
The VFD is in ”hand on” mode and
cannot be controlled right now.
Please set the VFD in automatic
mode by pressing the button “Auto
on”.
M
√
√
A112
Fan Alarm – VFD
Danfoss control
Undesired FAN control detected.
Please restart the VFD.
M
√
√
A113
Hardware alarm
Missing a jumper wire on digital
input 6. Between IN6 and +24V.
Only applicable with Filter Systems
without Fire Safety ShieldControl.
M
√
√