29
Set-up the operation of room thermostat in:
MENU
→
Boiler Settings
→
Room
thermostat
→
Thermostat Selection
→
Universal
Once the preset room temperature
has been reached, thermostat opens
its contacts and the display shows:
Once the temperature in the room, in which
the room thermostat is installed, has reached
the preset value, regulator reduces the
preset boiler temperature by the value set in
Inc. p. b. temp.thermostat
and the display
shows
. This will cause longer breaks in
boiler operation (the boiler will remain in
SUPERVISION mode) and the same,
temperature in heated rooms will drop.
Moreover, the boiler pump (CH pump) may
be interlocked for a certain time by opening
the contacts of the room thermostat in
heated rooms. To activate this function -
enter:
MENU
→
Boiler Settings
→
Room
thermostat
→
CH pump standstill
and set the value of this parameter >0.
Setting the value of e.g. ,,5” causes the
pump will be stopped by the room
thermostat for 5 min. When ,,0” is set, CH
pump will not be stopped by the room
thermostat. Once this time has elapsed, the
regulator switches on CH pump for a time set
in
CH pump op t. th. on
e.g. 30s. This
feature prevents from excessive cooling of
the system caused by pump stop.
Pump interlock by opening the
contacts of the room thermostat
may be activated only upon
making sure the boiler will not be
overheated.
11.11
Connection of mixer’s room
thermostat
This parameter is available in:
MENU Mixer Settings no. 1,2,3,4,5
Mixer pump does not stop upon opening the
contacts of the room thermostat unless other
settings have been made in Service Menu.
Select the value of this parameter so that
once the room thermostat has responded (its
contacts have opened), the temperature in
the room drops. Other settings - see sec.
7.15
11.12
Connection of reserve boiler
The regulator can control a reserve boiler
(gas- or oil-fired), eliminating the necessity
of enabling or disabling this boiler manually.
The reserve boiler will be enabled if the
temperature of the pellet boiler drops, and
disabled when the pellet boiler reaches an
appropriate temperature. Connection to a
reserve boiler, e.g. oil-fired one, should only
be made by a qualified fitter, in accordance
with the technical documentation of this
boiler.
The reserve boiler should be connected via
relay to terminals 30-31 as per drawing Fig.
25 oraz Fig. 27.
Fig. 27. Model diagram of layout for connecting a
reserve boiler to the ecoMAX800P1-L regulator, where:
1- regulator ecoMAX800P1-L module B 2 – reserve
boiler (gas- or oil-fired), 3 – Module U3, consisting of
relay RM 84-2012-35-1006 and base GZT80 RELPOL
In a standard version, the regulator is not
equipped with the U3 module.
You have to perform assembly
and installation of the module by
yourself, in conformity with the
applicable standards..