11 

 

7.8

 

OPERATION–Fuzzy Logic mode 

Upon  change  of  boiler  regulation  mode  from 

Standard  to

 

Fuzzy  Logic,

  regulator  works  in 

OPERATION  mode and modulates the boiler 
output  to  achieve  constant  preset  boiler 
temperature. 

Fuzzy  logic

  regulation  mode  may  be  set  in: 

MENU   Boiler Settings     Burner Settings  

 Regulation Mode 

 
Please  note 

Fuzzy  Logic

  program  is  adapted 

individually to the given boiler and fuel type 
and  may  work  properly  only  with  this  boiler 
and  fuel.  Therefore, 

Fuzzy  Logic

  mode 

requires  special  settings  and  has  to  be 
activated  by  the  boiler  manufacturer  in 
accordance with sec. 21.1

In case this mode 

has  not  been  activated,  it  will  not  be 
available. 

Fuzzy Logic correction

 

In some instances, Fuzzy Logic mode has to 
be adjusted to the fuel quality. To make the 
correction,  use  the  following  parameters: 

FL 

fuel correction

 and

 FL airfl. correction 

 which 

are available in: 
MENU   Boiler Settings     Burner Settings. 
At first adjust 

FL fuel correction. 

If the fuel is 

of  poor  quality  and  incompletely  burnt  fuel 
particles  are  present  in  ash,  reduce  the  rate 
of  supplied  fuel;  in  the  contrary  case  - 
proceed in analogical manner.  
Note:  incompletely  burnt  fuel  particles  or 
lowered  furnace  may  be  also  caused  by 
improper  boiler  operation  in  SUPERVISION  
mode.  Therefore,  prior  to  correcting 

Fuzzy 

logic

 it is recommended to adjust parameters 

of  SUPERVISION    mode  in  accordance  with 
sec. 7.9. 

 

Activation of 

Fuzzy Logic

 mode of 

regulation  does  not  release  from 
the  requirement  to  adjust  the 
parameters 

of 

SUPERVISION  

mode  –  risk  of  screw  feeder 
damage. 

Switching  off  output  modulation  in  Fuzzy 
Logic 
In  case  the  regulator  works  in  SUMMER 
mode  of  operation  or  with  a  little  heat 
demand (in Spring and Autumn), modulation 
of boiler output is not justified. To switch-off 
the  boiler  output  modulation  in 

Fuzzy  Logic

 

mode  of  regulation  -  set  both  parameters: 

Min.  boiler  output  FL 

and  Max.  boiler  output 

FL  at the same value - e.g. 80%. The boiler 
starts  operation  without  output  modulation 
and upon achievement of preset temperature 
enters SUPERVISION  mode. 

Boiler output in 

Fuzzy Logic

 

In  case  of  boiler  operation  in  conditions  of 
little  heat  demand,  fuel  consumption  may 
increase.  It  is  a  result  of  the  fact  that  the 
output  modulation  algorithm  reduces  boiler 
output  to  the  minimum,  at  which  boiler 
efficiency  is  much  lower  than  in  case  of  the 
rated  output.  In  such  instances,  it  is 
recommended  to  reduce  permitted  range  of 
boiler  output  so  that  it  will  not  work  at  the 
minimum  output.  The  range  of  boiler  output 
is  defined  by  the  parameters: 

Min.boiler 

output  FL 

and   

Max.boiler  output  FL 

 

available  in:  MENU 

  Boiler  Settings     

 

Burner Settings. 
E.g.: 

Min.boiler  output  FL  (Min.  moc  kotła 
FL)

=40% (factory setting: 0%) 

Max.boiler output FL =

100%(factory setting: 

100%) 

7.9

 

SUPERVISION  

SUPERVISION    mode  is  available  for  both 
modes  of  regulation:  with  manual  and 
automatic  settings  (

Fuzzy  Logic)

.  Regulator 

automatically  enters  SUPERVISION    mode 
without any user's intervention, namely: 
-  in  case  of 

Standard

  mode  of  regulation– 

upon 

achievement 

of 

boiler 

preset 

temperature, 
-  in  case  of 

Fuzzy  logic

  –  once  actual 

temperature  has  exceeded  the  boiler  preset 
temperature by 5°C.  
 

Содержание ecomaxx 800 R2

Страница 1: ...L BOILERS A B C functions chich are available in module respectively A B C room panel ecoSTER200 module B C and ecoSTER200 are not part of standard equipment SERVICE AND ASSEMBLY MANUAL ISSUE 1 3 SOFT...

Страница 2: ......

Страница 3: ...other changes in the boiler fittings which can influence the burning process The fittings should correspond to the components installed by the manufacturer p 21 It is recommended to operate boiler wit...

Страница 4: ...ENTS 22 11 3 INSTALLATION OF CONTROL PANEL 22 11 4 MOUNTING OF OPERATING UNIT 23 11 5 IP PROTECTION RATE 24 11 6 ELECTRIC CONNECTION 24 11 7 TEMPERATURE SENSORS CONNECTION 27 11 8 WEATHER SENSORS CONN...

Страница 5: ...gulator a boiler manufacturer should check if the regulator s mating with the given boiler type is proper and whether it can cause danger The regulator is not an intrinsically safe device which means...

Страница 6: ...ters It can be used in a household and similar facilities as well as in light industrialized facilities 3 Information about documentation The regulator manual is a supplement for the boiler manual In...

Страница 7: ...REGULATOR INSTRUCTION MANUAL ecoMAXX 800R2...

Страница 8: ...temperature decrease due to activated time spans Boiler preset temperature during loading the hot water boiler HW Boiler preset temperature increase from mixer circulation weather control switch on f...

Страница 9: ...RING UP mode press the knob and select FIRING UP This mode enables to control manually fan and fuel feeder Follow strictly the instructions of the boiler manufacturer when firing up the boiler Fig 5 M...

Страница 10: ...Blow in Output The feeder starts periodically and remains in operation for the duration set in Feeding Time then it stops and remains off over the time set in Feeder Interval 1 Fuzzy Logic mode of re...

Страница 11: ...ment to adjust the parameters of SUPERVISION mode risk of screw feeder damage Switching off output modulation in Fuzzy Logic In case the regulator works in SUMMER mode of operation or with a little he...

Страница 12: ...to OPERATION mode once actual boiler temperature has achieved preset value less boiler hysteresis Examples of SUPERVISION mode settings fuel hard coal Feeder Interval Superv 15 30min Feeding Time Supe...

Страница 13: ...C value of heating curve movement must be set for 5 C To reach room temperature 18 C value of heating curve paralel movement must be set for 2 C In this configuration a thermostat can be connected It...

Страница 14: ...preset mixer temperature to thermostat 0 In case of connected ecoSTER200 room control panel additionally set the parameter Room temperature coefficient 0 Guidelines for proper settings of heating curv...

Страница 15: ...tion of circulating pump using the parameter HUW Circulation Support in MENU Pump Service Settings 7 19 Grate In case the boiler is adapted to burn fuel on additional grate the feeder or the fan with...

Страница 16: ...bration If the service parameters of the boiler Feeder Efficiency and Tank Capacity are properly set calibration is not necessary regulator should properly calculate fuel level But if the fuel level c...

Страница 17: ...USER MANUAL OF CONTROLLER INSTALLATION AND SERVICE SETTINGS ecoMAXX 800 model R2...

Страница 18: ...using excessive number of elbows and cross section reductions and iii apply other rules of gravitational circuit construction e g keeping of gradients etc In case the return temperature sensor is of...

Страница 19: ...container 16 room thermostat or ecoSTER200 17 HUW circulating pump 27 return temperature sensor does not affect combustion process control 28 thermostatic 3 way valve 29 throttle mushroom valve RECOMM...

Страница 20: ...um temperature has been exceeded thermostat is not included in the regulator supply 27 return temperature sensor recommended mounting location bottom section of boiler water jacket 28 thermostatic 3 w...

Страница 21: ...hroom valve 32 HUW circulating pump 34 lower buffer sensor 35 upper buffer sensor 36 heat buffer 37 additional solar ecoSOL regulator Parameter Setting MENU OPERATION mode Return Protection OFF Servic...

Страница 22: ...ature of storage and transport should be within scope 15 65 degrees C During transport the controller can not be exposed to vibrations bigger than typical for transport of boilers 11 REGULATOR INSTALL...

Страница 23: ...oreover access of the user to live parts under hazardous voltage e g terminals shall be prevented Standard installation housing of a width of 8 modules as shown in a may be used In such case the user...

Страница 24: ...with protective wire in accordance with applicable regulations Caution After the regulator is turned off using the keyboard dangerous voltage can occur on the terminals Before starting any assembly wo...

Страница 25: ...sor CT4 T3 HUW temperature sensor T4 underfloor heating circuit sensor thermostatic valve without electric servo T room thermostat R reserve boiler AL alarm annunciator PP boiler shunt pump to protect...

Страница 26: ...rature sensor CT4 T5 out door temperature sensor type CT4 P T6 boiler return water temperature sensor RE relay 5 6V max 80mA to connect reserve boiler R alarm AL boiler shunt pump PP or HUW circulatin...

Страница 27: ...V AC PM mixer pump SM mixer servo PC HUW circulating time HUW circulating pump available in module C from software version mod_A_v 01 31 21 GR ground strip 11 7 Temperature sensors connection Wires of...

Страница 28: ...oller according to Pic 19 or properly to used kind of controller The sensor should be screw to the wall Acces to assembly holes is possible after unscrewing the cover of the sensor Fig 1 Weather senso...

Страница 29: ...ly upon making sure the boiler will not be overheated 11 11 Connection of mixer s room thermostat This parameter is available in MENU Mixer Settings no 1 2 3 4 5 Mixer pump does not stop upon opening...

Страница 30: ...he reserve boiler switches on Fig 28 8 Hydraulic diagram with reserve boiler connection of open and close circuits 1 ecoMAXX regulator 2 reserve boiler 3 U3 module 2 pcs 4 switching valve with limit s...

Страница 31: ...sensor damage Feeder temperature sensor damage No fuel AL 1 AL 2 AL 3 AL 4 AL 5 1 2 4 8 16 Example when this parameter is set at 8 voltage will be applied at the contact only upon occurrence of AL4 al...

Страница 32: ...ENU Information tab Mixer Info set other parameters of the mixer 11 15 Connection of mixer pump HUW circulating pump may be connected with the regulator in a few ways to the output H through relay acc...

Страница 33: ...l In case the limiter is not installed bridge the terminals 1 2 using wire of cross section area of min 1 mm2 and with insulation enough thick to meet safety requirements for the boiler 11 18 Connecti...

Страница 34: ...uded in the regulator supply Max length of wires to ecoSTER200 control panel depends on cross section area of a wire and e g for a wire of cross section of 0 25 mm2 it should not exceed 30m The cross...

Страница 35: ...equent boiler change over from SUPERVISION to OPERATION mode where fuel pouring or furnace lowering may occur Fuzzy Logic Fuzzy Logic settings are available only for boiler manufacturers Min preset bo...

Страница 36: ...has no effect on control of combustion process kg h Energy Density Parameter used to rough calculation of boiler output it has no effect on control of combustion process Its value for hard coal amoun...

Страница 37: ...been filled and HUW pump has been stopped a boiler overheating risk may occur It occurs in case the preset HUW temperature is higher than the preset boiler temperature This issue refers particularly t...

Страница 38: ...has two functions it enables preventing the user to set too high value of preset mixer temperature when the parameter Mixer support is set at FLOOR ON it determines the limit value of mixer temperatu...

Страница 39: ...ause unnecessarily servo motions while too high setting will increase time of finding preset temperature value Correct value should be determined experimentally Recommended settings of this parameter...

Страница 40: ...e temperature measured by HUW sensor is higher than Max HUW temperature HUW pump goes off In this manner users of hot utility water are protected from burning Alarm is reset by regulator switching off...

Страница 41: ...y decay In the cases of power supply failure the regulator will resume the operation mode in which it was before the failure 18 2 Protection against freezing If the boiler temperature drops below 5 C...

Страница 42: ...of operating unit Compatibility is guaranteed if first component of software ID number of the panel and of the operating unit is the same In following example software is compatible because first comp...

Страница 43: ...ked 4 The fan is inoperative If YES and the boiler temperature is lower than the preset value by DelT lack of fuel it is a normal condition related to detection of lack of fuel 5 Fuel feeder inoperati...

Страница 44: ...n SUPERVISION mode If YES adjust this mode acc sec 11 check whether too intensive combustion is caused by the setting Cycle order OPERATION see sec 35 if the regulator has the option of fuel type sele...

Страница 45: ...LERS TESTED IN THE PLUM LABORATORIES ARE COMPATIBLE WITH FITTINGS FOR SOLD BOILERS IT IS INADMISSIBLE TO REPLACE THE FEEDER AND FAN TO OTHER TYPES AS WELL AS MAKING OTHER CONSTRUCTIONAL MODIFICATIONS...

Страница 46: ...or supply 27 return temperature sensor recommended mounting location bottom section of boiler water jacket 28 thermostatic 3 way valve to protect boiler return 29 throttle mushroom valve 32 HUW circul...

Страница 47: ......

Страница 48: ...Ignatki 27a 16 001 Kleosin Poland tel 48 85 749 70 00 fax 48 85 749 70 14 plum plum pl www plum pl www plumelectronics eu...

Отзывы: