Automatic pump lock time 

0…60 

0min. 

Function saving electricity by stopping the pump of the regulated 
heating  circuit  when  the  measured  temperature  of  the circulating 
water is maintained for 15 minutes above the preset temperature 
water. Recommended setting: 15 min. 

Room thermostat

 

  Heating  circuit  lock 

time 

0 … 255

 

10 min. 

This parameter is applicable only in situation when for the heating 
circuit 

Pump  lock  from  room  thermostat

  =  Yes  and 

Room 

thermostat  function

  =  thermostat.  If  the  heating  source  is  locked 

by  room  thermostat,  it  will  be  unlocked  after 

heating  circuit  lock 

time 

for a 

heating circuit operation time

 although room thermostat 

still  does  not  allow  operation  of  the  heating  circuit.  Such  action 
prevents heated rooms against excessive temperature drops.

 

 

Heating 

circuit 

operation time

 

0 … 255

 

5 min. 

Notifications 

ON, OFF 

ON 

OFF

  -  allows  you  to  display  informational  messages  in  the  main 

window, 

ON

  -  does  not  allow  the  display  of  informational 

messages in the main window. 

Operation in HOLIDAY mode 

Temperature 

stabilization night 

Anti-freeze 

This  parameter  determines  whether  the  HOLIDAYS  mode  and 
OFF  mode  is  total  off  heat  receiver  (Anti-freeze)  or  the 
temperature is maintained at night. 

13.6

 

Solar 

Settings for the Solar are shown in the menu only when connected temperature sensors SL, SH 
and DHW. 

Solar

 

Name 

Range** 

Setting** 

Description 

Support 

OFF, ON 

 

ON  

OFF

 

– disables operation of solar circuit, 

ON 

– enables operation of 

solar circuit. 

Solar pump activation 
delta T 

1,5 … 20 

7°C 

When  difference  between  solar  collector  temperature  and  HUW 
lower temperature exceeds 

Solar pump activation delta T

 parameter 

value, solar pump will be activated.

 

Solar pump deactivation 
delta T 

1 … 19 

3°C 

When  difference  between  solar  collector  temperature  and  HUW 
lower  temperature  drops  below 

Solar  pump  activation  delta  T

 

parameter value, solar pump will be deactivated. 

Minimum collector 
temperature 

4 … 110 

10°C 

Solar pump will not be enabled below this temperature. If 

minimum 

collector temperature =

 0, function is disabled. 

Maximum collector 
temperature 

110 … 150 

120°C 

Above this temperature, solar pump will be enabled in order to cool 
the  solar  panel  provided  that  HUW  tank  temperature  is  lower  than 
the maximum value. If 

maximum collector temperature =

 0, function 

is disabled. 

Collector disable 
temperature 

130 

… 200 

15

0°C 

Above  this  temperature,  solar  pump  will  be  disabled  in  order  to 
prevent it against overheating. Pump will be enabled again after the 
solar  panel  is  cooled  down.  If 

collector  disable  temperature  = 

0, 

function is disabled. 

Minimum pump 
revolutions 

2

5 … 100 

15% 

If 

minimum  pump  revolutions

  =  0,  solar  pump  revolutions 

modulation  function  is  disabled  (pump  always  activates  with  100% 
revolutions). 
If 

minimum  pump  revolutions

  >  0,  solar  pump  revolutions 

modulation  function  is  enabled.  Function  enables  to  increase 
reception  of  heat  energy  from  the  solar  panel  at  low  insolation. 
Solar  pump  decreases  its  revolutions  when  difference  between 
temperatures between a solar collector sensor and HUW tank lower 
temperature drops.

 

Anti-freeze - Solar 

-3

5 … -15 

0

°C 

Solar  panel  temperature  at  which  the  anti-freeze  function  is 
activated. This value should be higher than freezing temperature of 
the  agent  inside  a  solar  circuit,  e.g.  glycol.  Solar  pump  is 
deactivated  when  solar  panel  temperature  drops  below 

Anti-freeze 

(solar) 

parameter  value.  It  causes  heat  reception  from  HUW  tank 

and  heating  the  solar  panel.  Caution:  enabling  this  function  can 
cause considerable heat energy losses. When 

Anti-freeze (solar) = 

“0”, anti-freezing function is disabled. 

Maximum HUW 
temperature 

40 

… 90 

55°C 

Maximum  set  temperature  of  water  in  the  tank.  This  parameter 
defines what temperature the HUW tank will be heated up to during 
the  solar  collector  is  loaded.  It  is  a  very  important  parameter 

Содержание ecoMAX920P2-I

Страница 1: ...FOR CENTRAL HEATING SYSTEMS OPERATION AND INSTALLATION MANUAL Manual version 1 0_EN 05 2019 ecoSTER TOUCH ecoNET300 ecoNET apk www econet24 com ecoSTER TOUCH and internet module ecoNET300 are not par...

Страница 2: ......

Страница 3: ...ANTI FREEZE 15 9 3 ROOM TEMPERATURE STABILIZATION 16 9 4 SOLAR 17 9 5 INTERNET 17 FOR THE INSTALLER 19 10 CONTROLLER ASSEMBLY 20 10 1 GENERAL REQUIREMENTS 20 10 2 OUTPUT MODULE ASSEMBLY 20 10 3 TEMPER...

Страница 4: ...ainst frozen central heating system Values of programmed parameters must be set in accordance with a particular building and hydraulic system The controller is not an intrinsically safe device It mean...

Страница 5: ...over to a new user or owner 5 Used symbols The following graphical symbols are used in the manual useful information and tips useful information concerning property damage health or life threat for p...

Страница 6: ...6...

Страница 7: ...CONTROLLER OPERATION MANUAL ecoMAX920P2 I FOR THE USER...

Страница 8: ...enables quick transportation of HUW to a bathroom or kitchen located far away Heating circuits The controller control the operation of one direct heating circuit radiator and two adjustable heating c...

Страница 9: ...mbol of active heat source this symbol indicates that the boiler is active 7 Heating mode symbol possible options day and night 8 Preset room temperature it is set separately for day and night mode Pr...

Страница 10: ...o get back to main window from every menu sublevel 3 Info button press to obtain detailed information concerning the parameter selected on a display 4 Press to enter service level for installer 7 6 In...

Страница 11: ...11 7 7 User s main menu Caution particular menu positions can be invisible in case there is no appropriate sensor module or setting...

Страница 12: ...HUW window click an arrow in controller main window element no 11 HUW preset temperature can be also entered in menu preset temperatures HUW tank loading function becomes active after connecting a ta...

Страница 13: ...perature drops below SUMMER mode deact temperature parameter Automatic switching into SUMMER mode is possible only when the external temperature sensor is connected 8 5 Work mode setting It is possibl...

Страница 14: ...nfluence on operation of HUW tank Enables a single HUW load in situation when HUW tank heat energy saving mode is active 1 x HUW loading User can select main mode for HUW tank as Inactive and if neces...

Страница 15: ...rameters i e when the controller is operated Day screen brightness between 06 00 22 00 Night screen brightness between 22 00 06 00 8 11 Software update Software can be modified with the use of microSD...

Страница 16: ...e pump will be stopped If it is lower than 13 C the pump will continue its operation and heating circuit will be heated by a heat source boiler up to a minimum value service parameter The pump will be...

Страница 17: ...ank work mode to Auto Define time program for HUW tank in such way to set insolation periods as night Due to this the boiler will not heat up the HUW tank Similar effect can be obtained by setting the...

Страница 18: ......

Страница 19: ...CONTROLLER ASSEMBLY AND SERVICE SETTINGS MANUAL ecoMAX920P2 I FOR THE INSTALLER...

Страница 20: ...ing provides the IP20 protection rating The casing on the connectors cover side provides IP00 rating and because of that connectors must be unconditionally covered with the cover If there is a need to...

Страница 21: ...rcuit pumps to the controller according to the electric scheme 10 6 Connecting servos Electrical servo is installed only when there is an adjustable heating circuit H2 circuit or H3 circuit The contro...

Страница 22: ...ong wall surface In service settings of each circuit assign the control panel to an appropriate heating circuit or a group of heating circuits for which it will serve as a room thermostat After the pa...

Страница 23: ...nd 2 adjustable H2 circuit 3 adjustable H3 circuit 4 control panel no 2 5 boiler 6 controller output module Names of room panel and heating circuits can be changed Maximum 6 room panels can be connect...

Страница 24: ...er it is recommended to increase heating curve parallel shift and decrease the heating curve if during frost room temperature is too low and too high when the weather is warmer it is recommended to de...

Страница 25: ...correction 0 Room thermostat deactivation In order to cause room thermostat to influence the set temperature of water in the heat circuit set room temperature correction parameter to 0 when room therm...

Страница 26: ...20 boiler with integrated pump 21 mechanical protective thermostat for protecting floor circuit against excessive water temperature 22 HUW tank lower temperature sensor lower solar sensor 23 solar col...

Страница 27: ...ling main heat source 35 C menu service settings System Additional heat source Pump start temperature 8 55 C menu service settings System Additional heat source Minimum temperature 50 C menu service s...

Страница 28: ...heat source Temperature deactivating main heat source 35 C menu service settings System Additional heat source Cooling temperature 92 C menu service settings System Additional heat source Minimum temp...

Страница 29: ...C menu service settings System Additional heat source Pump starting temperature 55 C menu service settings System Additional heat source Cooling temperature 92 C menu service settings System Addition...

Страница 30: ...settings System Main heat source Hysteresis heat source 5 C menu service settings System Main heat source Selection heat source boiler pellet menu service settings System Main heat source Pump operat...

Страница 31: ...13 weather sensor 14 HUW pump 15 HUW tank water temperature sensor 16 HUW circulating pump 17 solar pump 18 solar panel 19 controller control panel with room thermostat function 20 mechanical protect...

Страница 32: ...e setting System Main heat source Disabling the absence of heat demand YES menu service setting System Main heat source Selection Fireplace menu service setting System Additional heat source Pump star...

Страница 33: ...e menu service setting System Additional heat source Temperature deactivating main heat source 35 C menu service setting System Additional heat source Pump starting temperature 55 C menu service setti...

Страница 34: ...als 26 55 terminal RJ or USB will damage the controller and may cause electric shock Tips of connection cables especially mains voltage cables should be secured from splitting by e g insulated clamp s...

Страница 35: ...ector 2 protective strip 3 placing cable clamps in the housing they should be broken 4 cable outlets 5 improper cable connection 6 holdfast of the cable Electrical cables should be isolated from hot p...

Страница 36: ...g temperature of a fireplace with water jacket type CT 10 WS weather temperature sensor type CT6 P H0 S universal temperature sensor e g for measuring temperature of a heat buffer type CT 10 OUT V2 ou...

Страница 37: ...e heating curve shift Constant water preset temperature Decreasing constant water temperature Room thermostat selection No Panel 1 T1 T3 Room thermostat function Thermostat Temperature correction Room...

Страница 38: ...time Notifications Operation in HOLIDAY mode Solar Support Solar pump activation delta T Solar pump deactivation delta T Minimum collector temperature Maximum collector temperature Collector disable t...

Страница 39: ...rom the control panel and they have an effect on a preset temperature of water in the heating circuit Name Panel 1 can be changed in the main menu to e g Living room in case the panel is assembled in...

Страница 40: ...uit High temperature in the floor circuit can cause damage to flooring and scalding to users Adjustment method fixed value weather weather fixed value constant preset temperature of water in nonadjust...

Страница 41: ...an be used only when Room thermostat function thermostat Exceeding a set room temperature causes decreasing set temperature in the heat circuit by Decreasing water temperature from thermostat value Se...

Страница 42: ...loading at disabled heating circuits Extending HUW pump operation time 0 255 0 min After loading the HUW tank and disabling the HUW pump a risk of boiler overheat can occur Such risk is possible in a...

Страница 43: ...n Modulation 5K Modulation 10K Modulation 20K No modulation Setting No modulation the main source of heat works without output modulation Setting Modulation 5K Modulation 10K Modulation 20K the main h...

Страница 44: ...ps below Solar pump activation delta T parameter value solar pump will be deactivated Minimum collector temperature 4 110 10 C Solar pump will not be enabled below this temperature If minimum collecto...

Страница 45: ...The settings for the buffer are only visible in the menu after selecting the supported hydraulic diagram no 6 Solar Name Range Setting Description Valve switching temperature 25 80 55 C Temperature a...

Страница 46: ...adiation During transportation the controller cannot be subjected to vibrations exceeding normal vibrations generated during wheel transportation 9 It is a current consumed only by the controller Over...

Страница 47: ...47...

Страница 48: ...ul Wsp lna 19 Ignatki 16 001 Kleosin Poland plum plum pl www plum pl...

Отзывы: