30 

 

 

Connecting  emission  sensor:  1  –  exhaust  temp. 
sensor type CT2S, 2 – sensor lead, 3 – flue.

 

 

 

Caution:  Opening  the  boiler  door 
can 

cause 

the 

emission 

temperature to exceed the sensor‘s 
thermal resistance, which can burn 
the sensor out.  

12.11

 

Temperature sensors 

checking 

Temperature  sensors  can  be  checked  by 
measuring 

their 

resistance 

in 

given 

temperature.  In  case  of  big  differences 
between  measured  resistance  value  and 
values  in  table  below,  the  sensor  should  be 
replaced with a new one. 
 

 

CT4  

Temp.  

°C 

Min. 

Ω 

Nom. 

Ω 

Max. 

Ω 

802 

815 

828 

10 

874 

886 

898 

20 

950 

961 

972 

25 

990 

1000 

1010 

30 

1029 

1040 

1051 

40 

1108 

1122 

1136 

50 

1192 

1209 

1225 

60 

1278 

1299 

1319 

70 

1369 

1392 

1416 

80 

1462 

1490 

1518 

90 

1559 

1591 

1623 

100 

1659 

1696 

1733 

 

CT6-P (weather) 

Temp.  

°C

 

Min. 

Ω 

Nom. 

Ω 

Max. 

Ω 

-25 

901,6 

901,9 

902,2 

-20 

921,3 

921,6 

921,9 

-10 

960,6 

960,9 

961,2 

999,7 

1000,0 

1000,3 

25 

1096,9 

1097,3 

1097,7 

50 

1193,4 

1194,0 

1194,6 

100 

1384,2 

1385,0 

1385,8 

125 

1478,5 

1479,4 

1480,3 

150 

1572,0 

1573,1 

1574,2 

 

CT2S-2 (exhaust) 

Temp. 

°C 

Min. 

Ω 

Nom. 

Ω 

Max. 

Ω 

999,7 

1000,0 

1000,3 

25 

1096,9  1097,3 

1097,7 

50 

1193,4  1194,0 

1194,6 

100 

1384,2  1385,0 

1385,8 

125 

1478,5  1479,4 

1480,3 

150 

1572,0  1573,1 

1574,2 

12.12

 

Connection of optical sensor 

The  optical  sensor  should  be  connected  in 
accordance  with  the  electric  scheme, 
maintaining  the  polarization  of  the  SYG  (+) 
and  GND  (-)  signals  of  the  sensor.  Reading 
from  the  flame  optical  sensor  is  possible  in 
the menu:  
Information 

→ 

Flame 

 

Incorrect  connection  of  the  optical 
sensor 

will 

not 

damage 

the 

controller  or  the  sensor  itself,  but 
the  burner  flame  detection  will  be 
incorrect. 

12.13

 

Connection of mixers room 

temperature 

Room  thermostat  after  disconnecting  wires 
reduces  preset  temperature  of  the  value  of 
reduction  the  preset  temperature  of  the 
mixer  from  the  thermostat.  Parameter  is  in 
the menu: 
Mixer  settings  1-5 

  Mixer  room 

temperature 
Value of parameter should be chosen in such 
a way that after activating room thermostat, 
temperature in the room should decrease. In 
case  of  room  panel  make  sure  that  this 

220°C 

Содержание ecoMAX860P3-KL

Страница 1: ...EN_DRAFT OLNY APPLIES TO SOFTWARE MODULE A B PANEL v01 XX XX v01 XX XX 09 2019 functions available in the additional module B the ecoSTER TOUCH or ecoSTER200 room panel and ecoNET300 Internet module i...

Страница 2: ...lation etc check if the controller is not connected to the mains Installation should be done by a person with appropriate electrical qualifications Improper cables connection could result in the contr...

Страница 3: ...OUNTING OF MODULE 24 12 5 IP PROTECTION RATE 25 12 6 CONNECTING ELECTRICAL SYSTEM 25 12 7 ELECTRIC SCHEME 27 12 8 CONNECTION OF TEMPERATURE SENSORS 29 12 9 CONNECTION OF WEATHER TEMPERATURE SENSOR 29...

Страница 4: ...er and whether it can cause danger The controller is not an intrinsically safe device which means that in the case of malfunction it can be the source of a spark or high temperature which in the prese...

Страница 5: ...e manual We are not responsible for any damages caused by failure to observe these instructions 4 Storage of documentation This assembly and operation manual as well as any other applicable documentat...

Страница 6: ......

Страница 7: ...USER SETTINGS ecoMAX860P3 KL...

Страница 8: ...l level calibration Burner cleaning Lambda sensor calibration HUW settings Preset HUW temp HUW pump mode Off Priority No priority HUW cont hysteresis HUW disinfection Night time decrease Boiler Off Re...

Страница 9: ...oiler circuit active return protection increasing the preset temperature to load the buffer 5 signaling blowing operation 6 signaling fuel feeder operation 7 signaling CH pump operation 8 signaling HU...

Страница 10: ...the hot user water tank and power heating circuits of mixers 8 5 FIRE UP mode The FIRE UP mode is for automatic firing up of furnace in boiler Total time of firing up proces is dependand on controller...

Страница 11: ...uses power levels defined in Standard mode In this mode the parameters Average hysteresis H2 and MIN hysteresis H1 do not have to be set The Fuzzy Logic mode unlike the Standard mode is not faulty in...

Страница 12: ...ffer decrease of top buffer temperature below preset value Loading start temperature 8 11 GRATE Some boilers have an additional grate to burn other fuels such as wood waste etc To activate the grid mo...

Страница 13: ...automatic detection of summer mode is switched on user can set the parameters Activ temperature SUMMER so outdoor temp above which the summer mode will be switched on and Deactv temperature SUMMER so...

Страница 14: ...e it was described in previous point not recommended or automatically constantly correct heating cycle temperature It is not recommended to use both these possibilities at the same time Automatic corr...

Страница 15: ...time intervals is indicated by the symbol on the main screen To activate time intervals set the parameter Night time decrease for the given heating circuit to ON The parameter Reduction value set the...

Страница 16: ...y settings will not always correspond to actual fuel consumption so to work correctly this method needs level calibration by controller s user No additional fuel sensors are required Calibration Fill...

Страница 17: ...feeder or other device may cause danger 8 27 Cooperation with room panel The controller can cooperate with room panels All panels has a built in room thermostat This room panels shows useful informati...

Страница 18: ...18...

Страница 19: ...19 INSTALLATION AND SERVICE SETTINGS ecoMAX860P3 KL...

Страница 20: ...figure use large nominal diameter pipes and four way valve avoid unnecessary angles and reductions maintain a min 2 horizontal pipe slope etc If the sensor 3 is attached to the pipe isolate it with f...

Страница 21: ...CH and HUW settings Boiler pump YES Service settings CH and HUW settings Mixer 1 support CH ON Service settings Mixer 1 settings Max mixer 1 temp 70 C Service settings Mixer 1 settings Mixer 1 heatin...

Страница 22: ...gs Loading end temp 75 C Service settings Buffer settings Mixer 1 support CH ON Service settings Mixer 1 settings Max mixer 1 temp 70 C Service settings Mixer 1 settings Mixer 1 heating curve 0 8 1 4...

Страница 23: ...es connected to the controller During transport the device cannot be exposed to vibrations greater than those typical of normal road transport 12 Controller installation 12 1 Environmental conditions...

Страница 24: ...t exceeded the ventilation holes do not always guarantee that the temperature of the panel surroundings will be lowered in such case use other methods 12 4 Mounting of module Working module has to be...

Страница 25: ...sary to access the part with the terminals disconnect the mains supply make sure that there is no voltage on terminals and leads and remove the executive module enclosure 12 6 Connecting electrical sy...

Страница 26: ...served Controller should be equipped with a set of pins connected to the 230 VAC mains Connect protective wire of power supply cable to ground strip linked with metal boiler housing Connect coupling t...

Страница 27: ...P control panel HW HUW temp sensor type CT4 M1 mixer 1 temp sensor type CT4 WS weather temp sensor type CT6 P RS boiler water return temperature sensor type CT4 FS feeder temp sensor type CT4 OS flam...

Страница 28: ...ower 230 VAC GR grounding strip FU fuse PM2 PM3 mixer pump SM2 SM3 mixer servomotor CPU controlling A main controller connect exclusively with two cables do not connect with four cables as it may lead...

Страница 29: ...contact hot parts of the boiler and heating system Wires of temperature sensors are heat resistant to the temperature not exceeding 100 C 12 9 Connection of weather temperature sensor The controller...

Страница 30: ...5 0 1385 8 125 1478 5 1479 4 1480 3 150 1572 0 1573 1 1574 2 CT2S 2 exhaust Temp C Min Nom Max 0 999 7 1000 0 1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8 125 1478 5...

Страница 31: ...elay 12VDC consisting of relay RM 84 2012 35 1012 and base GZT80 RELPOL Standard version of the controller is not equipped with a relay Assembly of relay should be done by a person with proper qualifi...

Страница 32: ...r 2 external alarm annunciator 3 relay 12 17 Connectino of mixer servo During assembly works for mixer servomotor pay attention not to overheat the boiler This may happen when there is a limited flow...

Страница 33: ...properly connected 12 18 Connection of STB temperature limiter In order to prevent the boiler from overheating due to the controller malfunction an STB safety temperature limiter or any other appropr...

Страница 34: ...g time bunrnig off Cleaning airflow Cleaning exh fan Cleaning time Cleaning pause Supervision Supervision time Boiler output Cycle time Blow in output Exh fan output Grate Fuel detection time Flush ti...

Страница 35: ...er temp Max mixer temp Proportional range Integration time constant Valve opening time Pump off by therm Mixer input dead zone Output H OFF Cleaning Alarm Reserve boiler Shunt pump Additional feeder n...

Страница 36: ...to calibrate fuel level The controller process this data if calibration process of fuel level was not done After successful calibration of fuel level the controller does not process this value Feeder...

Страница 37: ...ctivates room thermostat for boiler ecoSTER T1 option available after connecting room panel boiler operation is dependent on room thermostat No1 in ecoSTER ecoSTER T2 option available after connecting...

Страница 38: ...sensor Parameter determines to what maximum temperature HUW container will be heated during cooling the boiler in alarm situations It is a very important parameter because setting too high value of i...

Страница 39: ...he movement of the mixer actuator Increasing this value results in the mixer reaching the set temperature faster Setting this parameter to excessive values causes deregulation of the temperature and u...

Страница 40: ...ing power to the controller Checking the temperature sensor is described in point 12 11 15 4 Feeder temp sensor damage Alarm appears when feeder sensor is damaged or by exceeding measuring scope of th...

Страница 41: ...was before stoppage 16 2 Antifreezing protection When temperature of the boiler decreases below 5 C CH pump will be activated enforcing circulation of boiler water It will delay the process of freezi...

Страница 42: ...umes It is not recommended to change these parameters if regulation time and stability of keeping preset amount of air on required level Periodical calibration of Lambda sensor readings can be necessa...

Страница 43: ...miter STB is connected to terminals 1 2 then check if the circuit is not cut off due to boiler overheating Check if feeder engine is not broken or damaged In case when engine work can be heard and fue...

Страница 44: ...44...

Страница 45: ...45...

Страница 46: ...46...

Страница 47: ...47...

Страница 48: ...48 ul Wsp lna 19 Ignatki 16 001 Kleosin Poland plum plum pl www pum pl...

Отзывы: