Supervision 

 

  Supervision time 

After  this  time,  when  the  controller  is  in  SUPERVISION  mode,  the 
controller  automatically  starts  burner  burning  off.  By  settings  =  0, 
SUPERVISION mode is deactivated. 

  Feed time 

Fuel  feeding  in  SUPERVISION mode.  It  has  influence  on  burner  power 
by operating in SUPERVISION mode. Attention: the value should be as 
small  as  possible,  just  to  keep  the  flame  burning.  Too  big  value  may 
cause to boiler overheating. 

  Cycle time 

Feeder operation time in SUPERVISION mode. 

Supervision cycle time

 = 

Supervision feeding time

 + feeder pause time in Supervision.. 

  Blow-in output 

Fan  power  in  %  during  operation  in  Supervision  mode.  Adjust  value  in 
such  a  way  to  burn  feeding  fuel  in  Supervision  mode  with  low  fumes 
emission. 

Min. airflow output 

Minimum  fan  power  in  %  which  can  be  chosen  by  the  user.  It  is  only 
used  to  limit  the  accessible  scope  of  fan  power.  It  is  not  used  in 
algorithm  of  controlling  the  fan.  It  should  be  possibly  small  to  allow  the 
fan to rotate slowly, without buzzing. 

Fuel detection time 

Time  is  measured  after  decrease  in  brightness  of  flame  below  value 

flame detection %

 

. After deducting this time the controller switches into 

firing up attempt. After 3 failed attempts, it reports alarm: “failed firing up 
attempt.

” 

No fuel detection time Tsp

 

The  countdown  begins  when  temperature  falls  below 

No  fuel  emission 

temperature.

 

After  this  countdown  the  controller  attempts  to  fire  up  the 

burner and after 2 failed attempts activates the “firing up failed” alarm.

 

No fuel emission temperature

 

The temperature below which the controller counts down the 

no fuel 

detection time.

 

Max. burner temperature 

Determines  maximum  temperature  of  feeder  when  there  is  alarm  of 
exceeding maximum feeder temperature. 

Additional feeder operation 
time 

Determines  additional  feeder  operation  time.  Feeder  is  attached  to 
additional  module  B.  After  this  time  additional  feeder  operation  is 
stopped  despite  disconnecting  joints  of  fuel  level  sensor.  Joints  of  fuel 
level sensor are located in additional module B. 

Cleaning the exchanger 

Determines  the  emission  temperature  limit  above  which  you  will  be 
prompted to clean the boiler’s heat exchanger. 

 

14.1

 

 BOILER SERVICE SETTINGS 

Boiler settings

 

 

Thermostat selection 

Options to choose from: 

 

Deactivated (deactivates room thermostat influence on boiler 
operation) 

 

Universal (activates room thermostat for boiler) 

 

ecoSTER200 T1 (option available after connecting room panel 
ecoSTER200, boiler operation is dependant on room thermostat 
No1 in ecoSTER200) 

 

ecoSTER200 T2 (option available after connecting room panel 
ecoSTER200, boiler operation is dependant on room thermostan No 
2 in ecoSTER200 

– on sensor CT7) 

 

ecoSTER200 T3 (option available after connecting room panel 
ecoSTER200, boiler operation is dependant on room thermostat 
No3 in ecoSTER200 

– on sensor CT7)  

Min. boiler  timep 

Minimum preset boiler temperaturę which can be set in user menu and 
minimum temp. which can be set automatically by controller, i.e. from 
night reductions etc.  

Max. biler time 

Maximum 

preset boiler temperaturę which can be set in user menu and 

minimum  temp.  which  can  be  set  automatically  by  controller,  i.e.  from 
night reductions etc. 

Reserve boiler  

Description in point 12.2 

Alarms 

Description in point 12.3  

Содержание ecoMAX850P1-V

Страница 1: ...ns available in additional module B functions available in additional module C MX 03 room panel ecoSTER200 non standard option USER MANUAL FOR MAINTENANCE AND INSTALLATION EDITION 1 1 APPLIES FOR HARD...

Страница 2: ...DITIONS 23 12 2 INSTALLATION REQUIREMENTS 23 12 3 INSTALLATION 24 12 4 ELECTRIC CIRCUIT CONNECTION 24 12 5 SAFETY CONNECTIONS 26 12 6 ELECTRIC SCHEME 26 12 7 TEMPERATURE SENSORS CONNECTION 27 12 8 WEA...

Страница 3: ...the feeder etc The controller is for boiler producers The boiler producer before its use should check if the cooperation between the controller and the boiler is correct and is not dangerous The contr...

Страница 4: ...r s manual of the controller is divided into two parts for the user and for the installer However in both parts vital information concerning safety is included That is why the user should get aquainte...

Страница 5: ...USER MANUAL OF THE CONTROLLER ecoMAX850...

Страница 6: ...ature SUMMER Mixer settings 1 2 3 4 5 Preset mixer temperature Mixer room thermostat Weather control mixer Heating curve Mixer Curve shift Room temperatur factor Night time decrease Boiler Mixer 1 Mix...

Страница 7: ...temperature decrease due to activated time spans C Boiler preset temperature during loading the hot water boiler HW M Boiler preset temperature increase from mixer circulation P weather control switc...

Страница 8: ...etting parameters of its operation MENU button without connecting it to the electrical power After making sure that fuel is in the silo and the hatch is closed the boiler can be switched on 8 4 BOILER...

Страница 9: ...ler settings Regulation mode Standard mode operation Boiler output regulation begins when boiler temperature approaches preset temperature i e when the boiler sensor reaches Preset boiler temperature...

Страница 10: ...rature of the boiler Operation and pause time of the feeder in SUPERVISION mode is set using following parameters Feeding time SUPERVISION Period time SUPERVISION and Air flush intensity SUPERVISION T...

Страница 11: ...following parameters to activate this function Menu HUW settings Auto detection SUMMER Activating temp SUMMER Deactivating temp SUMMER 8 14 HOT WATER FEEDER DISINFECTION The controller can automatical...

Страница 12: ...will move heating curve by 2 degrees C In some cases described in point 8 16 it can be necessary to adjust heating curve movement In this configuration room thermostat ecoSTER is able to reduce temper...

Страница 13: ...low and in warmer time too high it is recommended to reduce parameter heating curve parallel shift and choose higher heating curve Buildings which are poorly isolated require setting heating curve wi...

Страница 14: ...window of the display Pic 12 Signalling time periods 8 18 CIRCULAR PUMP CONTROL Settings are in MENU Night time decrease Circular pump oraz Menu Service settings CH and HUW settings Settings of time...

Страница 15: ...el level reaches expected minimum parameter value should be set this way Menu Boiler settings Fuel level Fuel level calibration Fuel level 0 8 20 COOPERATION WITH ADDITIONAL FEEDER After connecting ad...

Страница 16: ...cated in the top portion of the controller s main housing Power supply to the fan and feeder will be reactivated Attention Boiler overheating is an abnormal condition therefore the cause must be found...

Страница 17: ...19 USER MANUAL OF CONTROLLER INSTALLATION AND SERVICE SETTINGS ecoMAX850P...

Страница 18: ...y it is necessary to isolate it thermically from surroundings and improve thermal contact with pipe Preset silo temperature must be set so high to ensure thermal power for mixer cycle when at the same...

Страница 19: ...boiler settings Min preset boiler temperature 75 C menu service settings boiler settings CH pump activating temperature 55 C menu service settings CH and HUW settings Activating operation buffer servi...

Страница 20: ...e active menu service settings buffer settings Buffer loading start temperature 50 menu service settings buffer settings Buffer loading stop temperature 75 menu service settings buffer settings Mixer...

Страница 21: ...rays Temperature of storage and transport should be within scope 15 65 degrees C During transport the controller can not be exposed to vibrations bigger than typical for transport of boilers 12 CONTRO...

Страница 22: ...troller on assembly surface where 1 cover 2 base 3 screw for cover 4 plug 5 screw for assembly surface 6 assembly surface 12 4 ELECTRIC CIRCUIT CONNECTION The controller is adapted to current 230V 50H...

Страница 23: ...the controller should be led through cable glands Cable glands should be screwed Make sure that glands are correctly screwed by pulling wire Length of isolation of external tire of wires should be mi...

Страница 24: ...re sensor CT2S T7 mixer temperature sensor TB connection of mixer room thermostat P controlling panel ecoSTER200 room panel with room thermostat function replacing TB or TM D D connection to additiona...

Страница 25: ...ires of the sensors are resistant to temperature not exceeding 100 degrees C 12 8 WEATHER SENSORS CONNECTION The controller cooperates solely with weather sensor type CT4 P The sensor should be instal...

Страница 26: ...own on Pic 17 12 12 BOILER ROOM THERMOSTAT CONNECTION Room thermostat for boiler circuit can switch off the burner operation or switch off the CH boiler pump In order to thermostat switch off boiler o...

Страница 27: ...ng alarms compatible with alarm signal codes causes activation of additional boiler When pellet boiler is fired up and its temperature exceedes preset value i e 25 degrees C then controller switches o...

Страница 28: ...ller 2 external alarm device 3 transmitter Then in order to operate correctly set proper code for active alarms signal in menu Menu Service settings Boiler settings Alarms Choosing value 127 causes ac...

Страница 29: ...documentation Do not confuse opening direction with closing direction Connect electrical power to the controller and switch it into STAND BY mode Check if wires for mixer opening and closing are not s...

Страница 30: ...which has following functions Room thermostat controls up to 3 thermostats Controlling panel for the boiler Alarm signal Fuel level indicator 4 way connection Connect accordingly to point 12 6 2 way c...

Страница 31: ...e Poker p after bur offe Cleaning airflow Supervision Supervision time Feed time Cycle time Blow in output Min airflow output Fuel detection time Max burner temperature Additional feeder operation tim...

Страница 32: ...RATION feeder pause time Blow in for Min output kW Blow in output for minimum boiler output 30 Feeder efficiency Feeder fuel efficiency in kg h Energy density Fuel calorific in kWh kg Tank capacity Fu...

Страница 33: ...The temperature below which the controller counts down the no fuel detection time Max burner temperature Determines maximum temperature of feeder when there is alarm of exceeding maximum feeder temper...

Страница 34: ...when HW l Available after connecting HW sensor Prolonged feeding of HW silo during priority HW deactivated may cause to overcooling of the CH installation because CH pump is deactivated Parameter CH p...

Страница 35: ...e will be increased to load HW silo buffer and mixer cycle Temperature increase is only realizing when it is necessary When preset boiler temperature is at sufficient level then controller will not ch...

Страница 36: ...ature Parameter serves two functions allows restricting setting too high mixer preset temperatur Automatic control also will not cause exceeding preset temperature above value set in this parameter wi...

Страница 37: ...MP EXCEEDING This alarm occurs when the contact opens the feeder sensor The alarm is reset by turning the regulator The controller can not be used as sole protection of boiler against back fire Additi...

Страница 38: ...not protect the installation against freezing 17 3 PUMP ANTI STANDSTILL FUNCTION The controller does the function of CH HW and Mixer pumps protection against getting stale 17 4 NETWORK FUSE REPLACEMEN...

Страница 39: ...r in fumes It is not recommended to change these parameters if regulation time and stability of keeping preset amount of air on required level Periodical calibration of Lambda sond readings can be nec...

Страница 40: ...ition it should be unlocked by untwisting the cover and twisting the button according to documentation of boiler producer Check the fan and replace it if necessary 5 Additional ffeder is not working m...

Страница 41: ...rners should be consultet with Company Plum Sp z o o In order to load new parameters go to Menu service settings special password and choose proper boiler burner Default settings can also be loaded by...

Страница 42: ...48 7 7 964 556 4411 7 905 579 6633 8 963 695 44 11 E mail 5564411 mail ru 5564411 ooo bioterm ru...

Отзывы: