Supervision
Supervision time
After this time, when the controller is in SUPERVISION mode, the
controller automatically starts burner burning off. By settings = 0,
SUPERVISION mode is deactivated.
Feed time
Fuel feeding in SUPERVISION mode. It has influence on burner power
by operating in SUPERVISION mode. Attention: the value should be as
small as possible, just to keep the flame burning. Too big value may
cause to boiler overheating.
Cycle time
Feeder operation time in SUPERVISION mode.
Supervision cycle time
=
Supervision feeding time
+ feeder pause time in Supervision..
Blow-in output
Fan power in % during operation in Supervision mode. Adjust value in
such a way to burn feeding fuel in Supervision mode with low fumes
emission.
Min. airflow output
Minimum fan power in % which can be chosen by the user. It is only
used to limit the accessible scope of fan power. It is not used in
algorithm of controlling the fan. It should be possibly small to allow the
fan to rotate slowly, without buzzing.
Fuel detection time
Time is measured after decrease in brightness of flame below value
flame detection %
. After deducting this time the controller switches into
firing up attempt. After 3 failed attempts, it reports alarm: “failed firing up
attempt.
”
No fuel detection time Tsp
The countdown begins when temperature falls below
No fuel emission
temperature.
After this countdown the controller attempts to fire up the
burner and after 2 failed attempts activates the “firing up failed” alarm.
No fuel emission temperature
The temperature below which the controller counts down the
no fuel
detection time.
Max. burner temperature
Determines maximum temperature of feeder when there is alarm of
exceeding maximum feeder temperature.
Additional feeder operation
time
Determines additional feeder operation time. Feeder is attached to
additional module B. After this time additional feeder operation is
stopped despite disconnecting joints of fuel level sensor. Joints of fuel
level sensor are located in additional module B.
Cleaning the exchanger
Determines the emission temperature limit above which you will be
prompted to clean the boiler’s heat exchanger.
14.1
BOILER SERVICE SETTINGS
Boiler settings
Thermostat selection
Options to choose from:
Deactivated (deactivates room thermostat influence on boiler
operation)
Universal (activates room thermostat for boiler)
ecoSTER200 T1 (option available after connecting room panel
ecoSTER200, boiler operation is dependant on room thermostat
No1 in ecoSTER200)
ecoSTER200 T2 (option available after connecting room panel
ecoSTER200, boiler operation is dependant on room thermostan No
2 in ecoSTER200
– on sensor CT7)
ecoSTER200 T3 (option available after connecting room panel
ecoSTER200, boiler operation is dependant on room thermostat
No3 in ecoSTER200
– on sensor CT7)
Min. boiler timep
Minimum preset boiler temperaturę which can be set in user menu and
minimum temp. which can be set automatically by controller, i.e. from
night reductions etc.
Max. biler time
Maximum
preset boiler temperaturę which can be set in user menu and
minimum temp. which can be set automatically by controller, i.e. from
night reductions etc.
Reserve boiler
Description in point 12.2
Alarms
Description in point 12.3