17
OI remote control for Pluggit Avent
Englis
h
3.11.5. Setting temperatures for the bypass
(optional)
1. Switching on installer menu, see page 16.
2. Press button (1) at the right.
The set points for the outside air temperature T1 (2) and
the exhaust air temperature T3 (3) start flashing.
3. Press centre of button (1).
The set point for T1 (2) flashes quicker.
4. Press top or bottom of button (1) until the desired set
point (8-15 °C) is reached.
5. Press centre of button (1).
The setting is saved and the set point for T3 (3) flashes
quicker.
6. Press top or bottom of button (1) until the desired set
point is reached.
7. Press centre of button (1).
The setting of the set point is saved and the new set
points for T1 (2) and T3 (3) are displayed.
8. Hold down button (1) at the right for approx. 10 seconds.
The installer menu is closed.
3.11.6. Setting sensitivity of the humidity sensor
(optional)
If a humidity sensor (accessory) is used, the sensitivity can
be adjusted for the automatic programme.
If the set point for the relative air humidity is set too low, this
may cause impairments of the inhabitants' well-being and
may cause certain materials in the building to dry out.
However, if the set point is set too high, this may cause
moisture damage in the structure of the building and may
as well impair the inhabitants' well-being.
1. Switching on installer menu, see page 16.
2. Press centre of button (1).
The most recently selected automatic programme (2)
flashes.
3. Press centre of button (1). The most recently selected
set point (3) will flash.
4. Press top or bottom of button (1) until the desired set
point is reached.
5. Press centre of button (1).
The setting is saved.
6. Hold down button (1) at the right for approx. 10 seconds.
The installer menu is closed.
3.11.7. Setting the sensitivity of the VOCs sensor
(optional)
If a VOC sensor (accessory) is used, the sensitivity can be
adjusted for the automatic programme using the
Pluggit iFlow.
Die Wohnraumlüftung
RH%
1
2
3
M+P-26A-0983
Note:
For further information on handling the Pluggit iFlow,
please refer to the operating and installation instruc-
tions of the room ventilation unit.
Low sensitivity
Degree of pollution (ppm)
600
900
1200
Medium sensitivity
Degree of pollution (ppm)
550
800
1000
High sensitivity
Degree of pollution (ppm)
500
750
800
Die Wohnraumlüftung
RH%
2
1
3
M+P-26A-0980