16
BIA AeroFresh Plus
5. Press SELECT button.
ChEC
is displayed. The LED corresponding to the SE-
LECT button and the LED corresponding to SET button
flash.
6. Press SELECT button when the individual components
are not to be manually confirmed.
The SEr programme restarts
7. Press SET button when the individual components of the
humidifier are to be manually confirmed.
8. Press SELECT button.
P
is displayed.
9. Press SET button. The humidifier can be switched on or
off.
on
--> switch on humidifier
oF
--> switch off humidifier
10. Press SELECT button.
In
is displayed.
11. Press SET button. The water inlet valve can be opened or
closed.
on
--> open water inlet valve
oF
--> close water inlet valve
12. Press SELECT button.
dr
is displayed.
13. Press SET button. The water outlet valve can be opened
or closed.
on
--> open water outlet valve
oF
--> close water outlet valve
14. Press SELECT button.
Co
is displayed.
15. Press SET button. The contactor can be switched on or
off.
on
--> switch on contactor
oF
--> switch off contactor
16. Press SELECT button.
rEL
is displayed.
17. Press SET button. The signal relay can be switched on or
off.
on
--> switch on signal relay
oF
--> switch off signal relay
18. Press SELECT button.
The
SEr
programme restarts.
19. Press MODE button.
The
SEr
programme is terminated.
5.2.2.
"Adjustments" programme
The following features can be set in the AdJ programme:
•
Set steam output.
•
Set controller signal of the hygrothermal transducer.
•
Set switching-on threshold.
1. Repeatedly press MODE button until the display shows
AdJ
.
2. Press SELECT button.
OL
is displayed.
3. Press SET button. The steam output can now be set.
Setting range:
25
oo
-100
oo
It is set to 100 % as default.
4. Press SELECT button.
CS
is displayed.
5. Press SET button. The controller signal of the hygro-
thermal transducer can be set.
Setting range V:
on.oF
;
0-20
;
0-16
;
0-10
Setting range mA:
i
0.20
;
i
4.20
4.20
is set as default.
6. Press SELECT button.
tP
is displayed.
7. Press SET button. The switching-on threshold can be
set.
Setting range:
10
oo
-20
oo
It is set to 20 % as default.
8. Press SELECT button.