4
Power Quality. Voltage fluctuations and Flicker.
The requirement is specified in section
5.4.2, test procedure in Annex A or B 1.4.3
Starting
Stopping
Running
dmax
[%]
dc [%]
d(t)
[%]
dmax
[%]
dc [%]
d(t)
[%]
Pst
Plt 2
hours
Measured Values
0.36
0.3
0
0.36
0.3
0
0.133
0.058
Normalised to
standard
impedance
and 3.68kW for
multiple units
2.21
1.84
0
2.21
1.84
0
0.82
0.36
Limits set under
BS EN 61000-3-2
4%
3.30%
3.3%
500ms
4%
3.30%
3.3%
500ms
1
0.65
Test start date
2017-06-14
Test end date
2017-06-14
Test location
No.8 Chunxin East Road, Wuxi, Jiangsu
Power quality. DC injection.
The requirement is specified in section 5.5, test procedure in
Annex A or B 1.4.4
Test power level
10%
55%
100%
Recorded value(mA) 1.1404
3.6546
3.1117
as % of rated AC
current
0.05%
0.16%
0.14%
Limit
0.25%
0.25%
0.25%
Power Quality. Power factor.
The requirement is specified in section 5.6, test procedure in
Annex A or B 1.4.2
216.2V
230V
253V
Measured at three voltage levels
and at full output. Voltage to be
maintained within ±1.5% of the
stated level during the test.
Measured value
0.9962
0.9959
0.9951
Limit
>0.95
>0.95
>0.95