Process Level Technology, Ltd.
MAG-GAGE
®
OPS-001 Revision 6
Page
26
of
30
December 17, 2018
Section 4.3.0. – Electric Level Switches (MGS-200EX/MGS-200EX2)
Caution:
If there is a need to take the switch out of service or disconnect it for any reason, then make the sure
the circuit is de-energized.
Note:
Keep cover tightly closed when in operation. To prevent ignition of GRP. B atmospheres a approved
sealing fitting must be installed
4.1.5 ELECTRICAL WIRING – RISING LEVEL
N/O
Red
Terminal 1
Closes on rising level.
C
Green
Terminal N
N/C
Blue
Terminal 2
Opens on rising level.
4.1.6 ELECTRICAL WIRING – FALLING LEVEL
N/C
Red
Terminal 1
Opens on falling level.
C
Green
Terminal N
N/O
Blue
Terminal 2
Closes on falling level.
(N) Green
(1) Red
(2) Blue
Electronic Level Control
Installation, Operation and Maintenance Instructions