User manual - DRR450
25
23
H.b.a.d.
Heater Break Alarm Delay
Heater Break Alarm activation delay
Word modbus 2023
0…3600 seconds. >
Default
: 60.
24
coo.f.
Cooling Fluid
Type of refrigerant fluid for heating / cooling P.I.D.
Word modbus 2024
0
Air. >
Default
.
1
Oil
2 Water
25
p.b.m.
Proportional Band Multiplier
Word modbus 2025
100…500 hundreths. >
Default
: 100.
Es. 100 = 1.00
26
ou.d.b.
Overlap/Dead Band
Dead band combination for heating / cooling P.I.D.
Word modbus 2026
-20.0…50.0 % in tenths. >
Default
: 0.
Negative: dead band.
Positive: overlapping.
Es. 100 = 10.0%
27
co.c.t.
Cooling Cycle Time
Cycle time for cooling output.
Word modbus 2027
1…300 seconds. >Default: 10.