![Pixsys DRR450 Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/pixsys/drr450/drr450_user-manual_1560838023.webp)
User manual - DRR450
23
14
t.c.
Cycle Time
Cycle time (for P.I.D. on SSR 1”).
Word modbus 2014
1…3000 tenths of second >
Default
: 10.
Es. 10 = 1.0 seconds
15
L.L.o.p.
Lower Limit Output Percentage
Selects min. value for command output percentage.
Word modbus 2015
0…100% >
Default
: 0%.
16
u.L.o.p.
Upper Limit Output Percentage
Selects max. value for command output percentage.
Word modbus 2016
0…100% >
Default
: 100%.
17
deGr
Degree
Selects degree type.
Word modbus 2017
0
Centigrades. >
Default
.
1
Fahrenheit.
18
aL. 1
Alarm 1 selection.
The alarm intervention is related to AL1.
Word modbus 2018
0
Disabled. >
Default
.
1
Absolute alarm, referring to process
2
Band alarm
3
Upper deviation alarm
4
Lower deviation alarm
5
Absolute alarm, referring to command setpoint
6
Status alarm (active in Run / Start)
7
Cooling output
Содержание DRR450
Страница 1: ...DRR450 Controller Regolatore User manual Manuale installatore...
Страница 2: ......
Страница 62: ...62 DRR450 Manuale d uso...
Страница 63: ......