User manual - DRR227 -
19
21
Sft.G.
Softstart Gradient (Password 5678)
Rising gradient for Soft-Start
0 Disabled.
Default
1-9999 (degrees/hour).
24
S.tim.
Softstart Time (Password 5678)
Max. Softstart duration: the process will follow the gradient only for the time set
on parameter, than moves to the max. power.
00.00 Disabled.
Default
00.01-24.00 hh.mm
25
dGt.i.
Digital Input (Password 1234)
Digital input functioning (see par. 7.7)
dis.
Disabled (
Default
)
2.Spv
2 setpoint thresholds
run
Run
tunE
Tune (impulsive digital input). Parameter 8
P.i.d.
must be set as
MAn.
Au.MA.
Automatic/Manual
Act.t.
Regulation type
o.rSt
Output reset (impulsive digital input)
26
d.i.c.t.
Digital Input Contact Type (Password 1234)
Select the digital input inactive contact.
o.c.
Open contact (
Default
)
c.c.
Closed contact
27
AL.1
Alarm 1 (Password 1234)
Alarm 1 selection.
dis.
Disabled (
Default
)
A. AL.
Absolute / threshold, referring to process
b. AL.
Band alarm
H.d.AL.
Upper deviation alarm
L.d.AL.
Lower deviation alarm
28
A.I.5.o
Alarm 1 State Output (Password 1234)
Alarm 1 output contact and intervention type.
n.o. s.
(N.O. Start) Normally open, active at start (
Default
)
n.c. s.
(N.C. Start) Normally closed, active at start
n.o. t.
(N.O. Threshold) Normally open, active on reaching alarm
1
n.c. t.
(N.C. Threshold) Normally closed, active on reaching alarm
1
1
On activation, the output is inhibited if the controller is in alarm mode. Activates only if alarm
condition reappers, after that it was restored..