Document 15342 Rev D1 07/24/97 P/N 15342:D1
Appendix A
ACM-8R and the System 5000
Capabilities
When installed with a System 5000, the ACM-8R can follow the status of initiating and
indicating circuits, relays, and several system control functions.
Circuits:
IZM-8 Initiating Device Circuits (alarm and trouble)
ICM-4/ICE-4 Indicating Appliance Circuits (activation and trouble)*
CRM-4/CRE-4 Control Relays (activation)*
TCM-2 circuits (activation and trouble)*
TCM-4 circuits (activation and trouble)*
VCM-4/DCM-4 circuits (activation and trouble)*
AIM-200 zones (alarm and trouble)
CPU Points: Activated Notification Circuits 1 and 2, the Remote Signaling Municipal Tie
circuit, and the Alarm Relay.
* Activation shown when System 5000 has been programmed to display "Output Status"
Software Required
To operate the ACM-8R, the Control Panel must be operating under CPU software with
the following part number (or greater):
System 5000 Board
U4 ROM Part Number
Central Processing Unit (CPU-5000)
73263
Trouble Indication
Communication between the CPU and ACM-8Rs (Not set for Receive Only Operation)
is accomplished over a two-wire EIA-485 serial interface. This communication circuit is
supervised by the Control Panel. Loss of communication results in "System Trouble" and
"Annunciator or Module Trouble" indications at the CPU.