For the System 500, System 5000,

AFP-200, AM2020, AFP1010 and

SFP-1024

Fire Alarm Control Panels

The

ACM-8R

Annunciator

Control

Module

P/N 15342:D1     ECN 97-304

12 Clintonville Road
Northford, CT 06472
203-484-7161
FAX: 203-484-7118

www.PDF-Zoo.com

firealarmresources.com

Содержание Notifier ACM-8R

Страница 1: ...97 Revision 07 24 97 Revision 07 24 97 Revision D1 For the System 500 System 5000 AFP 200 AM2020 AFP1010 and SFP 1024 Fire Alarm Control Panels The ACM 8R Annunciator Control Module P N 15342 D1 ECN...

Страница 2: ...unit Follow the instructions in the installation operating and pro grammingmanuals Theseinstructionsmustbefollowedtoavoid damage to the control panel and associated equipment FACP operation and relia...

Страница 3: ...nciators 12 Figure 3 4 ACM 8R Relay Terminal Assignments 13 Table 3 1 Relay Assignments 14 Mapping the ACM 8R relays 14 Row and Module Arrangement 15 Relay Assignment Examples 15 Figure 3 5 Connecting...

Страница 4: ...rcuit including AFM Series annunciators LDM Series annunciators LED 10N annunciators and UDACTs Universal Digital Alarm Communicator Transmitter EIA 485 bus compatible accessories are designed to prov...

Страница 5: ...Note for AM2020 installations only SIB 2048 can support two EIA 485 circuits each capable of spanning 6 000 feet 16 AWG For more details refer to Appendix B ACS and the AM2020 Wiring Specifications T...

Страница 6: ...configured for Receive Only operation they cannot send information to the system such as Module Trouble indications Wiring to Receive Only annunciators may be supervised by installing the modules ups...

Страница 7: ...on between the negative battery terminals of each supply must be made Fire Alarm Control Panel Power Loop EIA 485 Circuit EIA 485 Circuit Annunciator in a Backbox powered from Control Panel A common t...

Страница 8: ...M 8R draws its power from the control panel and must be considered when calculating the primary and secondary power supply requirements for the system Each annunciator module must be accounted for in...

Страница 9: ...ive screws on the top of the relay module and the two mounting holes on the bottom of the relay module with the pem standoffs on the backbox Secure with captive screws at top and with two loose screws...

Страница 10: ...ve 25 VRMS motor control circuits or SCR power circuits All enclosures including the FACP backbox must be connected to earth ground Never use the shield for grounding purposes Terminate the EIA 485 sh...

Страница 11: ...2 Set ON if the ACM 8R is to function in Receive Only mode on the EIA 485 circuit ALM RCV ONLY ONLY MODE SELECT SW4 TENS ONES SW1 SW2 ADDRESS SELECT SW3 Relay Assignment DIP Switches refer to Table 3...

Страница 12: ...ting screw on the backbox or cabinet Connect 24 VDC Power to the annunciator This power must be power limited but need not be supervised by a power supervision relay since it is inherently supervised...

Страница 13: ...map these relays will be assigned refer to Table 3 1 For information on wiring limitations refer to the UL Power limited Wiring Requirements section Figure 3 4 ACM 8R Relay Terminal Assignments Normal...

Страница 14: ...7 40 41 44 45 48 49 52 52 56 57 60 61 64 Table 3 1 Relay Assignments per EIA 485 address Mapping Note Note that Table 3 1 outlines relay assignments at a given EIA 485 address A single EIA 485 address...

Страница 15: ...le arrangement Note This correlation exists for each EIA 485 address That is the third cabinet row would become the 1st cabinet row at address 02 SW3 Cabinet Row select one only Set ON for 1st row Set...

Страница 16: ...ny module in the Sys tem 5000 To assign the ACM 8R to a mod ule two switches on SW3 must be set to ON Example To as signtheACM 8Rtothe thirdmoduleinthesec ond row of a System 5000 set switches 3 and 6...

Страница 17: ...modulehalfintheSys tem 5000 To assign the ACM 8R to a mod ule half two switches on SW3 must be set to ON The two switches that must be set ON are indicated below themodulehalf Example To assign theACM...

Страница 18: ...ght hand L series board set switches 3 and 6 on SW3 to ON set the other six switches to OFF 2 6 3 6 Address 01 Relay Assignment Example System 500 Alarm Trouble Mode The ACM 8R can follow the alarm an...

Страница 19: ...assis EIA 485 Loop 1 EIA 485 Loop 1 EIA 485 Loop 2 EIA 485 Loop 2 EIA 485 to ACM 8R TB2 3 EIA 485 to ACM 8R TB2 2 CPU 500 EIA 485 to ACM 8R TB2 3 EIA 485 to ACM 8R TB2 2 CPU 5000 EIA 485 Connection Th...

Страница 20: ...do not cut jumper JP5 The total amount of current drawn from these terminals cannot exceed that rating in standby or in alarm 24 VDC Power to ACM 8R TB1 2 Common to ACM 8R TB1 4 MPS 24B Main Power Su...

Страница 21: ...d circuits Different applications may require different conduit knockouts to be used Any conduit knockouts may be used provided that the nonpower limited wiring remain separated from the power limited...

Страница 22: ...e CPU Points Activated Notification Circuits 1 and 2 the Remote Signaling Municipal Tie circuit and the Alarm Relay Activation shown when System 5000 has been programmed to display Output Status Softw...

Страница 23: ...t of the CPU 5000 Note that an annunciator cannot be used to execute manual ON OFF control of intelligent AIM 200 points The option provides annunciation of up to 256 points for the System 5000 broken...

Страница 24: ...tions Software Zones 1 240 XP Series Transponder System Power and Audio Supply Supervision XPP 1 Form C Alarm and Trouble Relays XPC Control XPM Monitor and XPR Relay Module Circuits Software Required...

Страница 25: ...st be programmed from the AM2020 AFP1010 before the ACM 8R will function The AM2020 AFP1010 employ the following format for annunciator points A xx P yy Annunciator address Annunciator points in the r...

Страница 26: ...Points Activated Notification Circuits 1 and 2 the Remote Signaling Munici pal Tie circuit and the Alarm Relay Trouble Indication Communication between the CPU and the ACM 8R is accomplished over a t...

Страница 27: ...s eight system points and software zones Z1 through Z56 are automatically mapped to annunciator address 01 points 1 through 64 A1P1 A1P64 Zones Z57 through Z99 are mapped to annunciator address 02 poi...

Страница 28: ...Switches 3 On 5 On ACM 8R Dip Switches 4 On 5 On ACM 8R Dip Switches 1 On 6 On ACM 8R Dip Switches 2 On 6 On ACM 8R Dip Switches 3 On 6 On ACM 8R Dip Switches 4 On 6 On Annunciator Address 01 AFP 200...

Страница 29: ...Dip Switches 4 On 5 On ACM 8R Dip Switches 1 On 6 On ACM 8R Dip Switches 2 On 6 On ACM 8R Dip Switches 3 On 6 On ACM 8R Dip Switches 4 On 6 On ACM 8R Dip Switches 1 On 7 On ACM 8R Dip Switches 2 On 7...

Страница 30: ...e Up to 32 ACM 8R Relay Control Modules may be placed onto the EIA 485 communication bus if no other devices are installed on the bus CAUTION It is vitally important that following relay programming a...

Страница 31: ...1 y a l e R 2 Z 2 y a l e R R 8 M C A d n 2 3 Z 3 y a l e R N O 2 3 W S 4 Z 4 y a l e R N O 5 3 W S 5 Z 5 y a l e R F F O s r e h t o l l A 6 Z 6 y a l e R 7 Z 7 y a l e R 8 Z 8 y a l e R 9 Z 1 y a l...

Страница 32: ...W S 3 Z 3 y a l e R 7 y a l e R N O 5 3 W S 4 Z 4 y a l e R 8 y a l e R F F O s r e h t o l l A 5 Z 1 y a l e R 5 y a l e R R 8 M C A h t 4 6 Z 2 y a l e R 6 y a l e R N O 4 3 W S 7 Z 3 y a l e R 7 y...

Страница 33: ...ACM 8R for Receive Only SW4 2 ON and the other for Receive Transmit SW4 2 OFF Set switch SW3 on one ACM 8R so that SW3 2 ON and SW3 5 ON and the remaining switches are OFF Set SW3 on the other ACM 8R...

Страница 34: ...maining SW3 switches to OFF On the last ACM 8R set SW3 1 ON SW3 6 ON and the remaining SW3 switches to OFF Refer to the following charts 4 2 0 1 P F S e n o Z R 8 M C A m r a l A y a l e R R 8 M C A e...

Страница 35: ...M 8R module contains eight relays two ACM 8R modules are required for 10 zones Set the Mode Select switch SW4 for alarm only on both ACM 8Rs SW4 1 ON Set the first ACM 8R on the bus for Receive Only S...

Страница 36: ...se ACM 8Rs are set to address 03 Set the Mode Select switch SW4 for alarm only on both Alarm Only ACM 8Rs SW4 1 ON Set the first ACM 8R with address 03 for Receive Only SW4 2 ON and the second ACM 8R...

Страница 37: ...set to Address 03 Alarm Only Receive Only Receive Transmit SW3 2 ON SW3 5 ON SW4 1 ON SW4 2 ON SW3 3 ON SW3 5 ON SW4 1 ON SW4 2 OFF SW3 3 ON SW3 5 ON SW4 1 OFF SW4 2 ON SW3 4 ON SW3 5 ON SW4 1 OFF SW4...

Страница 38: ...38 38 38 38 38 Document 15342 Rev D1 07 24 97 P N 15342 D1 Notes www PDF Zoo com firealarmresources com...

Страница 39: ...39 39 39 39 39 Document 15342 Rev D1 07 24 97 P N 15342 D1 www PDF Zoo com firealarmresources com...

Страница 40: ...only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the...