Energy saving sensor (DWE) Instruction manual
(Switch operation sequence)
Adsorption command
(Sensor input)
COMMAND
Release valve
(Solenoid valve)
SW2
(Sensor output)
Atmospheric
pressure
Vacuum
Detected
pressure
After unlocking state from operation
mode press (▼) button for 4seconds
Press (▼) and (▲) button for more than
1second
PS : Display set switch mode
HL : Display set SW mode
dL : Display set filter mode
Po : Display set power save mode
no : Display set password mode
CP : Display set copy function mode
The PS entered in the selection mode will
display Press (▼) button each time will
show PS→HL→dL→Po→no→CP→PS in order
Press (▼) and (▲) simultaneously for more
than 1seocnd for mode you wish to set
The selection is confirmed and enters
each setting mode.
The setting item "P1" and the setting value "-90" are displayed in turn.
Pressing (▼) or (▲) button will show P1 P2 H1 HL Un dL Po no AP CP P1.
setting item and set value From any item, pressing (▼)and(▲)simultaneously for 1seocnd
will bring back to operation mode
47
SW1
(Sensor output)