background image

 9

  

·

Wrap t

ape material along the wire

 and

 seal wiring holes,

 to

 prevent 

entrance of c

ondensed water and insects.

·

Tightly

 

secure

 

the

 

power

 

source

 

wiring using

 

the

 

cord

 

clamp

 

inside

 

the

 

unit

.

Note: Fix

 

the

 

rubber

 

bushes

 

with

 

adhesive

 

when conduit

 

tubes

 

to

 

the

 

outdoor

 

unit

 

are

 

not

 

used

.

General

 

C

heck

(1)

Make

 

sure

 

that

 

the

 

field

-

selected

 

electrical components

 (

main

 

power

 

switches

circuit breakers

wires

conduit

 

connectors

 

and

 

wire

 

terminals

have

 

been

 

properly selected

 

according

 

to

 

the

 

electrical

 

data

.

Make

 

sure

 

that

 

the

 

components

 

comply with

 

National

 

Electrical

 

Code

 (

NEC

).

(2)

Check

 

to

 

ensure

 

that

 

the

 

voltage

 

of

 

power supply

 

is

 

within

 +

10

of

 

nominal

 

voltage and

 

earth

 

phase

 

is

 

contained

 

in

 

the

 

power supply

 

wires

If

 

not

electrical

 

parts

 

can

 

be damaged

.

(3)

Check

 

to

 

ensure

 

that

 

the

 

capacity

 

of

 

power supply

 

is

 

enough

.

If

 

not

the

 

compressor

 

will

 

be

 

not

 

able

 

to operate

 

due to abnormal

 

voltage

 

drop at

 

start

up

.

(4)

Check

 

to

 

ensure

 

that

 

the

 

earth

 

wire

 

is connected

.

(5)

Install

 

a

 

main

 

switch

,

 multi

-

pole

 

main

 

switch

,

 

with

 

a

 

space

 

of

 

0.14 in. (3.5mm)

 

or

 

more, single 

-

p

hase

 

main

 

switch

 

with

 

a

 

space

 

of 0.12 in. (3.0mm) or

 

more

 

between

 

each

 

phase

.

(6)

Check

 

to

 

ensure

 

that

 

the

 

electrical resistance

 

is

 

more

 

than

 

2

 

M

Ω, 

by measuring

 

the

 

resistance

 

between

 

ground and

 

the

 

terminal

 

of

 

the

 

electrical

 

parts

.

 If

 

not

do

 

not

 

operate

 

the

 

system

 

until

 

the electrical

 

leakage

 

is

 

located

 

and

 

repaired

.

·

Turn

 

OFF

 

the

 

main

 

power

 

switch

 

to

 

the

 

indoor

 

unit

 

and

 

the

 

outdoor

 

unit

,

 

and

 

wait

 

for 

at least

 

3

 

minutes

 

before

 

electrical

 

wiring work

 

or

 

a

 

periodical

 

check

 

is

 

performed

.

·

Check

 

to

 

ensure

 

that

 

the

 

indoor

 

fan

 

and

 

the outdoor

 

fan

 

have

 

stopped

,

 

before

 

electrical

 

wiring

 

work

 

or

 

a

 

periodical

 

check

 

is 

performed

.

·

Protect

 

the

 

wires

electrical

 

parts

etc

from rats

 

or

 

other

 

small

 

animals

If

 

not

 

protected

rats

 

may

 

gnaw

 

at

 

unprotected

 

parts

 

and

 

in the

 worst

-case scenario

a

 

fire will

 

occur

.

·

Prevent

 

the

 

wirings

 

from

 

touching

 

the

 

refrigerant

 

pipes

plate

 

edges

,

 

and

 

electrical parts

 

inside

 

the

 

unit

.

If

 

not

 

do

ne so

the

 

wires

 

will

 

be

 

damaged

 

and

 

in

 the

 

worst

-case scenario

a

 

fire

 

will

 

occur

.

·

Install

 

an

 

ELB

 

(Electric Leakage Break)

 at

 

the

 

power

 

source

.

If

 

an 

ELB

 

is

 

not

 

used

it

 

can

 

cause

 

electric

 

shock

 

or fire

 

at

 

the

 

worst

-case scenario

.

·

This

 

unit

 

uses

 

an

 

inverter

which

 

means

 

that

 

it

 

must

 

use

 

an

 

earth

 

leak

 

detector

 

capable

 

of 

hand

l

ing

 

harmonics

 

in

 

order

 

to

 

prevent

 

malfunctioning

 

of

 

the

 

earth

 

leak

 

detector

 

itself.

·

Do not use intermediate connection wires, stranded wires(see 

Attentions

 

when

 

Connect

ing

 the 

P

ower

 S

upply

 W

iring

),

 

extension cables or control line connection, 

as

 the use of these wires may

 

cause 

unwanted heat

, electric

 

shock

or fire.

·

The tightening torque of each screw shall be as follows.

M4

:

 0.7

 

to

 

1.0

 

lb

f

·

ft

(1

.

0

 

to

 

1

.

3

 

N

·

m)

M5

1.5 to 1.8 lb

f

·

ft

.

 (2

.

0

 

to

 

2

.

5

 

N

·

m)

M6

3.0 to 3.7 lb

f

·

ft

.

 (4

.

0

 

to

 

5

.

0

 

N

·

m)

M8

6.6 to 8.1 lb

f

·

ft

.

 (9

.

0

 

to

 

11

.

0

 

N

·

m)

M10

13.3 to 217 lb

f

·

ft

.

 (18

.

0

 

to

 

23

.

0

 

N

·

m)

Keep

 

the

 

above

 

tightening

 

torque

 values in mind

 

when

 

performing 

wiring

 

work

.

WARNING

CAUTION

Installation 

I

nstructions

Wiring

Содержание YH024GHFI18RT2

Страница 1: ...efully before installing or operating your new air conditioning system Be sure to save this manual for future reference Installation Manual CENTRAL SPLIT AIR CONDITIONER HIGH EFFICENCY CONDENSING UNIT Models YH024GHFI18RT2 YH036GHFI18RT2 YH060GHFI18RT2 R 410A REFRIGERANT 208 230 V 1 Phase 60Hz 18 SEER ...

Страница 2: ...This page intentionally left blank ...

Страница 3: ...gerant Flow Diagram 3 Diagram of Refrigerant Cycle Wiring 3 Refrigerant Flow Diagram 3 Electrical Wiring Diagram 3 Installation Instructions 4 Transportation and Handling Before Installation 4 Installation Location Selection 4 Drainage Elbow and Drain Hose Installation 5 Outdoor Unit Installation 5 Refrigerant Piping 6 Wiring 9 Test Run 11 Mode Outdoor Operation Temperature Range Maximum Minimum C...

Страница 4: ... COULD result in severe personal injury or death CAUTION Hazards or unsafe practices which COULD result in minor personal injury or product or property damage Carefully store the indoor and outdoor unit manuals away for your future reference Installation should be performed only by qualified personnel Improper installation can cause water leakage electrical shock or fire Install the air conditione...

Страница 5: ...arried out under the supervision of the person competent and capable in the handling of flammable refrigerants Means for disconnection such as circuit breaker which can provide full disconnection in all poles must be incorporated in the fixed wiring in accordance with the wiring rules It is necessary to allow the disconnection of the appliance from the supply after installation Ensure the disconne...

Страница 6: ...hanger EEV Service Valve Power Supply Power Supply Thermostat Thermostat Indoor Unit Indoor Unit Outdoor Unit Outdoor Unit Power Terminal Panel Power Terminal Panel Refrigerant Flow Diagram L2 L2 L1 L1 W W1 W2 B B C C R R Y Y G G G G R R C C C C B B Y Y W W W1 W1 W2 W2 Electrical Wiring Diagram Wiring single stage auxiliary heating thermostat Wiring twin stage auxiliary heating thermostat 3 Note a...

Страница 7: ...0 ft away from the antenna of a TV set or radio An amplifier may be required for the affected device Install the unit horizontallyandlevel Install it in an area not affected by snowfall or blowing snow If areas with heavy snow cannot be avoided install a canopy a pedestal and or some baffle boards Avoid the following places for installation where air conditioner related issues are liable to occur ...

Страница 8: ...ter to public places to avoid skidding 6 A strong base made of concrete etc should be made beforehand The appliance should be placed no less than 10 cm high to avoid getting wet or corroded Otherwise it can cause damage to the appliance or reduce its lifetime Fig 3 Drainage Elbow and Drain Hose Installation Outdoor Unit Installation Install Drainage Elbow and Drain Hose The condensate water may dr...

Страница 9: ... 1 32 0 8 1 32 1 0 1 32 0 8 1 32 0 8 1 32 1 0 1 32 1 0 1 Prepare locally supplied copper pipes 2 Use clean copper pipes Ensure that there is no dust or moisture inside of the pipes Blow the inside of the pipes with nitrogen or dry air to remove any dust or foreign materials before connecting pipes 3 Piping thickness and material of the pipe are shown as below Refrigerant Additional Charge The unit...

Страница 10: ...ing brazing c After brazing cool joint using the wet rag Installation Instructions Welding Torch Baffle Wet Cloth Piping Insulation Procedure Insulation field supplied 3 After finishing connection of the refrigerant pipes keep it warm using the insulation material as depicted in the figure on the right For the outdoor unit side insulate every piping end including valves Cover piping joints with pi...

Страница 11: ...halogen leak detector to check the flare nut and brazing points of leak Use foam that does not generate ammonia NH3 in the reaction Indoor Unit Outdoor Unit Manifold Valve Pressure Gauge Vacuum Pump Fig 9 2 Turn the cylinder upside down when filling Stand the cylinder upright when filling There is a siphon pipe inside so the cylinder need not be upside down to fill with liquid Filling Using a Cyli...

Страница 12: ...n power switch to the indoor unit and the outdoor unit and wait for at least 3 minutes before electrical wiring work or a periodical check is performed Check to ensure that the indoor fan and the outdoor fan have stopped before electrical wiring work or a periodical check is performed Protect the wires electrical parts etc from rats or other small animals If not protected rats may gnaw at unprotec...

Страница 13: ...Transmitting Cable to wired controller 1 Remove the screws maintenance plate and the valve cover 2 Pass transmitting cable and power supply through the two holes on the right side plate 3 Fasten the conduit connection to the right side plate using the lock nut 4 Connect the transmitting cable and power supply to the terminal 5 Secure the transmitting cable and power supply together with the clamp ...

Страница 14: ...ppliance is generally finished after the above operations are done If you still have any trouble please contact the local technical service center of our company for further information CAUTION Test Run Electrical Data Max Running Current A REFER TO NAMEPLATE Note 1 Follow local codes and regulations when selecting field wires All of the above are the minimum wire size 2 When transmitting cable le...

Страница 15: ...This page intentionally left blank ...

Страница 16: ...r Davis HVAC International Inc Parker Davis HVAC International Inc 3250 NW 107 Avenue Doral FL 33172 USA Tel 305 513 4488 Fax 305 513 4499 E mail info pd hvac com Website www pd hvac com Pioneer product line parts and supplies are available online for convenient ordering at www highseer com www pioneerminisplit com Scan the below code to visit our support page where you can find more installation ...

Отзывы: