58
F02
Interrupted or shorted upper
(supply) temperature sensor.
1. Check the electrical connection to the appropriate temperature sensor.
2. If connection is okay, replace bad sensor.
F03
Interrupted or shorted lower
(return) temperature sensor.
F05
Upper (supply) temperature
sensor exceeds 210
o
F.
1. If water in tank is not greater than 210
o
F, check wiring. Repair if faulty.
2. If wiring is okay, check appropriate sensor with ohmmeter and compare to reading in
resistance chart above. If reading does not agree with water temperature, replace bad
sensor.
F06
Lower (return) temperature
sensor exceeds 210
o
F.
F09
No flame detected – Heater
will make three attempts at
ignition before the control
goes into this lockout
condition. Will reset in 1
hour.
1. Watch the igniter through the observation window provided.
2. If there is no spark, check the spark electrode for the proper ¼” gap.
3. Remove any corrosion from the spark electrode and flame rectifier probe.
4. If there is a spark but no flame, check the gas supply to the heater.
5. If there is a flame, check the flame sensor.
6. Check any flue blockage or condensate blocks.
F10
Loss of flame signal – The
heater will relight 4 times
before the control goes into
this lockout condition. Will
reset in 1 hour.
1. Monitor the gas pressure to the unit while in operation.
2. Assure that the flame is stable when lit.
3. Check to see if the green light on the display module is out while the heater is running.
4. If the green light doesn’t come on or goes off during operation check the flame signal
on the status menu.
5. If the signal reads less than 1 microampere, clean the flame rectifier probe.
6. If the flame rectifier probe continues to read low, replace it.
F11F
False flame signal – The
heater will lock out if it
senses a flame signal when
there should be none
present.
1. Turn the gas off to the unit at the service valve.
2. If the flame signal is still present replace the igniter.
3. If the flame signal is not present after turning off the gas supply, check the gas valve
electrical connection.
4. If there is no power to the gas valve, remove the valve and check for obstruction in the
valve seat or replace the gas valve.
5. Turn the gas on at the service valve after corrective action is taken.
F13
Combustion fan speed
incorrect – The heater will
lock out if it senses that the
fan speed is less than 70% of
expected rate for more than
60 seconds.
1. Check the combustion air fan wiring.
2. Replace the combustion air fan.
3. Replace the control board.
pp
Parameters programmed
Press {S4} reset for at least 1 second.
F31
Program parameter error
Control must be re-programmed. If programming does not solve problem, control must
be replaced.
Table 16 - NOTE: If you replace a part to remedy a fault, it is recommended that you cycle the unit at least
three or four times to assure the fault has been resolved.
Содержание PHR100-55
Страница 12: ...12 PART 3 DIMENSIONS AND CLEARANCES Figure 1 LP 325 L ...
Страница 59: ...59 Figure 22 ...
Страница 60: ...60 Figure 23 ...
Страница 62: ...62 ...
Страница 63: ...63 ...
Страница 64: ...64 MAINTENANCE NOTES ...