Wiring
Operating Manual PSSu E S INC 24V se(-T)
1001380-EN-04
32
– Functional earth: 2.5 mm
2
(AWG12)
}
On base modules with screw terminals:
– If you use a multi-strand cable to connect the I/Os, it is recommended that you use
ferrules conforming to Parts 1 and 2 of DIN 46228, 0.14 ... 1.5 mm
2
, Form A or C,
although this is not essential. To crimp the ferrules you can use crimp pliers (crimp
form A or C) conforming to EN 60947-1, such as the PZ 1.5 or PZ 6.5 from
Weidmüller, for example.
– Maximum torque setting: 0.8 Nm
}
Use copper wiring.
6.2
Terminal configuration
Base module
Terminal configuration
Screw terminals:
PSSu BP 2/16 S
PSSu BP 2/16 S-T
Cage clamp terminals:
PSSu BP 2/16 C
PSSu BP 2/16 C-T
Without C-rail:
11: Input A
21: Input B
31: Input C
41: Input G (Gate)
12-22: 0 V encoder
(12-22 linked within the base
module)
32-42: Input S (Status)
(32-42 linked within the base
module)
13-23-33-43: Shield connec-
tion
(13-23-33-43 linked within
the base module)
14-24: Supply voltage output
for encoder
34: Output for limit value
monitoring
44: Input L (Latch)
21
11
22
12
23
13
24
14
41
31
42
32
43
33
44
34