Technical Details
Operating Manual PSSu E S 2AI RTD(-T)
22017-EN-07
36
Analogue inputs
312490
314490
Measuring ranges
Type
Pt100
Pt100
Measuring range
-200 - 850 °C
-200 - 850 °C
Type
Pt200
Pt200
Measuring range
-200 - 850 °C
-200 - 850 °C
Type
Pt500
Pt500
Measuring range
-200 - 850 °C
-200 - 850 °C
Type
Pt1000
Pt1000
Measuring range
-200 - 850 °C
-200 - 850 °C
Type
Ni100
Ni100
Measuring range
-60 - 250 °C
-60 - 250 °C
Type
Ni120
Ni120
Measuring range
-60 - 250 °C
-60 - 250 °C
Type
Ni1000
Ni1000
Measuring range
-60 - 250 °C
-60 - 250 °C
Type
Resistance
Resistance
Measuring range
0 - 4000 Ohm
0 - 4000 Ohm
Input filter
Digital filter
Digital filter
Filter time per input (2-wire meas-
urement) with attenuation
Attenuation
90 dB (60 Hz)
90 dB (60 Hz)
Filter time
103 ms
103 ms
Attenuation
80 dB (50 Hz)
80 dB (50 Hz)
Filter time
122 ms
122 ms
Attenuation
65 dB (50 Hz, 60 Hz)
65 dB (50 Hz, 60 Hz)
Filter time
122 ms
122 ms
Attenuation
69 dB (50 Hz, 60 Hz)
69 dB (50 Hz, 60 Hz)
Filter time
202 ms
202 ms
Attenuation
74 dB (50 Hz, 60 Hz)
74 dB (50 Hz, 60 Hz)
Filter time
482 ms
482 ms
Voltage measurement
Input resistance
100 MOhm
100 MOhm
Max. continuous voltage
5 V
5 V
Temperature measurement
Value of least significant bit
(LSB)
0,0625 K
0,0625 K
Resistance measurement
Value of least significant bit
(LSB)
0,0625 Ohm
0,0625 Ohm
Typ. conversion time per input
404 ms
404 ms
Max. measuring current
500 µA
500 µA
Deviations from the measuring
range limit value
Output variable error at 25
℃
0,3 %
0,3 %
Temperature coefficient
0,0040 %/K
0,0040 %/K