Function description
Operating Manual PSSu E F PS1(-T)
21298-EN-06
16
INFORMATION
Further information on the structure and contents of the status byte can be
found under “Operation”.
4.3.3
FS error behaviour
In the case of a safety-related error on an FS output, all FS outputs in the affected I/O-
Group (SafetyBUS p) are shut down.
In the case of a safety-related error on an FS input, the process image of all FS inputs in
the affected I/O-Group (SafetyBUS p) is set to zero.
The I/O-Group switches to a STOP condition. An error telegram is then triggered on Safety-
BUS p and the error is entered in the PSSuniversal error stack.