Technical details
Operating Manual PSS67 IO1 16FDI
1004417-EN-03
31
Inputs
Number
16
Voltage at inputs
24 V DC
Input current range
2,4 - 3,1 mA
Min. threshold voltage when signal changes from "1"
to "0"
8,2 V
Max. threshold voltage when signal changes from "0"
to "1"
10 V
Max. processing time of input when signal changes
from "1" to "0"
1 ms
Max. processing time of input when signal changes
from "0" to "1"
1 ms
Min. processing time of input when signal changes
from "1" to "0"
0,5 ms
Min. processing time of input when signal changes
from "0" to "1"
0,5 ms
Potential isolation between input and internal module
bus voltage
No
Test pulse outputs
Number of test pulse outputs
16
Voltage, test pulse outputs
24 V DC
Short circuit-proof
yes
Number of outputs that can be configured as test
pulses
16
Max. output current at "1" signal
0,25 A
Max. cable length between test pulse output and in-
put
200 m
SafetyNET p interface
Number
2
IP address (automatically off)
169.254.X.Y
Connection
M12
Transmission rates
100 MBit/s
Set via
Automatic
Max. number of FS-Tx and FS-Rx connections
64
Cycle time (t_SNp RTFN)
2 ... 60 000 ms
Max. number of variables with elementary FS data
types
4000
Environmental data
Climatic suitability
EN 60068-2-1, EN 60068-2-14, EN 60068-2-2, EN
60068-2-78
Ambient temperature
In accordance with the standard
EN 60068-2-14
Temperature range
0 - 60 °C
Storage temperature
In accordance with the standard
EN 60068-2-1/-2
Temperature range
0 - 60 °C
Condensation during operation
Permitted