PNOZ X4
Operating Manual PNOZ X4
19894-EN-07
18
Relay outputs
774730
774731
774734
External contact fuse pro-
tection, auxiliary contacts
Max. melting integral
240 A²s
240 A²s
240 A²s
Blow-out fuse, quick
10 A
10 A
10 A
Blow-out fuse, slow
6 A
6 A
6 A
Blow-out fuse, gG
10 A
10 A
10 A
Circuit breaker 24 V
AC/DC, characteristic
B/C
6 A
6 A
6 A
Contact material
0,2 µm Au
0,2 µm Au
0,2 µm Au
Conventional thermal
current while loading
several contacts
774730
774731
774734
Ith per contact at UB AC;
AC1: 240 V, DC1: 24 V
Conv. therm. current
with 1 contact
–
8 A
8 A
Conv. therm. current
with 2 contacts
–
7,5 A
7,5 A
Conv. therm. current
with 3 contacts
–
6,5 A
6,5 A
Ith per contact at UB DC;
AC1: 240 V, DC1: 24 V
Conv. therm. current
with 1 contact
8 A
–
–
Conv. therm. current
with 2 contacts
8 A
–
–
Conv. therm. current
with 3 contacts
7 A
–
–
Times
774730
774731
774734
Switch-on delay
With automatic start
typ.
270 ms
210 ms
210 ms
With automatic start
max.
600 ms
350 ms
350 ms
With automatic start
after power on typ.
270 ms
240 ms
240 ms
With automatic start
after power on max.
600 ms
390 ms
390 ms
With manual start typ.
70 ms
55 ms
55 ms
With manual start max.
600 ms
350 ms
350 ms
With monitored start
typ.
40 ms
30 ms
30 ms
With monitored start
max.
70 ms
50 ms
50 ms