PNOZ X4
Operating Manual PNOZ X4
19894-EN-07
17
Relay outputs
774730
774731
774734
Utilisation category of
auxiliary contacts
AC1 at
240 V
240 V
240 V
Min. current
0,01 A
0,01 A
0,01 A
Max. current
8 A
8 A
8 A
Max. power
2000 VA
2000 VA
2000 VA
DC1 at
24 V
24 V
24 V
Min. current
0,01 A
0,01 A
0,01 A
Max. current
8 A
8 A
8 A
Max. power
200 W
200 W
200 W
Utilisation category
In accordance with the
standard
EN 60947-5-1
EN 60947-5-1
EN 60947-5-1
Utilisation category of
safety contacts
AC15 at
230 V
230 V
230 V
Max. current
5 A
5 A
5 A
DC13 (6 cycles/min) at
24 V
24 V
24 V
Max. current
7 A
7 A
7 A
Utilisation category of
auxiliary contacts
AC15 at
230 V
230 V
230 V
Max. current
5 A
5 A
5 A
DC13 (6 cycles/min) at
24 V
24 V
24 V
Max. current
7 A
7 A
7 A
Utilisation category in ac-
cordance with UL
Voltage
240 V AC G. P.
240 V AC G. P.
240 V AC G. P.
With current
8 A
8 A
8 A
Voltage
24 V DC Resistive
24 V DC Resistive
24 V DC Resistive
With current
5 A
5 A
5 A
Pilot Duty
B300, R300
B300, R300
B300, R300
External contact fuse pro-
tection, safety contacts
In accordance with the
standard
EN 60947-5-1
EN 60947-5-1
EN 60947-5-1
Max. melting integral
240 A²s
240 A²s
240 A²s
Blow-out fuse, quick
10 A
10 A
10 A
Blow-out fuse, slow
6 A
6 A
6 A
Blow-out fuse, gG
10 A
10 A
10 A
Circuit breaker 24V
AC/DC, characteristic
B/C
6 A
6 A
6 A