Commissioning
Operating Manual PNOZ mmc4p
1002424EN02
15
INFORMATION
The transmission rate cannot be changed during operation.
6.5
Setting the station address
The station address of the expansion module PNOZ mmc4p is set from 0 ... 63 (binary) us
ing DIP switches 1 to 32.
Station address
DIP switch
32
16
8
4
2
1
0
Off
Off
Off
Off
Off
Off
1
Off
Off
Off
Off
Off
On
2
Off
Off
Off
Off
On
Off
3
Off
Off
Off
Off
On
On
...
...
...
...
...
...
...
62
On
On
On
On
On
Off
63
On
On
On
On
On
On
6.6
Download modified project to the PNOZmulti safety system
As soon as an additional expansion module has been connected to the system, the project
must be amended using the PNOZmulti Configurator. Proceed as described in the operat
ing instructions for the base unit.
NOTICE
For the commissioning and after every program change, you must check
whether the safety devices are functioning correctly.