6-3
6.2
Preparing for operation
6
Commissioning
Connection examples for semiconductor outputs
*Two loads may be connected to each safety output with advanced fault
detection, even on applications in accordance with EN IEC 62061, SIL
CL 3. Prerequisite: Feedback loop is connected, shorts across contacts
and external power sources are excluded (e.g. through separate multi-
core cables). Please note that, in the event of an error in the feedback
loop, the safety system switches to a safe condition and shuts down all
the outputs.
Connection examples for feedback loop
Redundant output
Single output
Single output with advanced fault de-
tection*
Feedback loop
Redundant output
Contacts from external contactors
K2
L-
O0 (O2)
O1 (O3)
K1
L-
K3
L-
K4
O0 (O2)
O1 ( O3)
K1
L-
K2
K1
L+
L-
K2
O0 (O2)
O1 (O3)
I0
L-
K1
L+
L-
K2
O0 (O2)
O1 (O3)
IM0
L-