Commissioning
Operating Manual PNOZ m EF 1MM
1003108-EN-11
| 40
To avoid EMC interference we recommend that the shield on the sensor cable is connected
to earth at
C
or
E
. However, depending on the application, it may be helpful to establish the
connection to functional earth at another point (in this case
A
or
B
).
Conductor loops outside the shield must be avoided.
If a shielded junction box is not used, the shield must run continuously from the sensor to
the evaluation device.
EMC-compliant wiring for connecting an encoder with drive
A
C
E
Drive
Encoder
Base Module
PNOZmulti 2
Shielded Connection Box
and
Adapter cable
Power
Supply
PNOZmulti 2
L1 N PE
Cabinet
Din-Rail
Power Supply
from Drive
A1 A2
X12
GND
Motion
Monitoring
Module
To avoid EMC interference we recommend that the shield on the sensor cable is connected
to earth at
C
or
E
. However, depending on the application, it may be helpful to establish the
connection to functional earth at another point (in this case
A
).