Function description
Operating Manual PNOZ m EF 1MM
1003108-EN-11
| 14
In PNOZmulti Configurator 12 areas can be configured per axis (with units < Version 2.0
only 8 limit values can be configured).
A tolerance range may also be set for the limit values used to monitor the speed. This toler-
ance range modifies the set limit values. As a result, one-off or periodic overshoots that ex-
ceed the limit values can be tolerated.
The following values can be configured for the tolerance range:
}
Tolerance time (t1), which takes into account the length of the overshoots (maximum time
for which the limit value may be exceeded). It must not be possible that the sum of all the
overshoots exceeds the tolerance time (t1) within a tolerance period (t2).
}
Tolerance period (t2), which takes into account the oscillation period (minimum time that
must elapse between one limit value overshoot and the next)
}
Tolerance amount (%), which takes into account the amplitude of the overshoots (max-
imum permitted percentage by which the configured limit values may be exceeded)
Tolerance amount (%)
Limit value
Speed
+
Tolerance amount (%)
t
v
Limit value
Speed
-
SSM
SSM
t
s
t
e
Enable SSM
0
1
Legend:
}
Enable SSM:
– "1": Monitored limit value not exceeded
– "0": Monitored limit value exceeded
}
t
s
: Speed v exceeds the limit value and activates the tolerance range (tolerance time, tol-
erance period, tolerance amount)
}
t
1
: Tolerance time
}
t
2
: Tolerance period
}
Tolerance amount (%): Tolerance amount of limit value in both directions