![Pilz 772 160 Скачать руководство пользователя страница 28](http://html1.mh-extra.com/html/pilz/772-160/772-160_operating-manual_1556635028.webp)
Commissioning
Operating Manual PNOZ m EF 4AI
1004650-EN-02
| 28
2-wire connection, supply voltage of sensors externally
}
The supply connections 24 V and 0 V are used only to supply the analogue input module.
}
The terminals I0- … I3- and 0 V must be bridged.
}
The 0 V connections of the external power supplies have to be interconnected.
I0+
I0-
PNOZ m EF 4AI
24V
0V
I1+
I1-
Sensor (SIL2)
+
-
I2+
I2-
24V
0V
I3+
I3-
24V
0V
Sensor (SIL2)
11
+
-
X1
, X
3
X2
,
X4
Sensor (SIL2)
+
-
Sensor (SIL2)
11
+
-
=
~_
L+
L-
0V
24 V
=
~_
L+
L-
24V
0V
24 V- Sensor
24 V- Sensor
24 V- Sensor
24 V- Sensor
24 V- Sensor
4-wire connection, supply voltage of sensors via analogue input module
}
Supply connections 24 V and 0 V are used to supply the analogue input module and to
supply the sensors.