PNOZ s60
Operating Manual PNOZ s60
1004492-EN-01
| 22
Times
750600
750601
751600
751601
Switch-on delay
With automatic
start typ.
20 ms
20 ms
20 ms
20 ms
With automatic
start max.
30 ms
30 ms
30 ms
30 ms
With automatic
start after power
on typ.
700 ms
700 ms
700 ms
700 ms
With automatic
start after power
on max.
800 ms
800 ms
800 ms
800 ms
With manual start
typ.
20 ms
20 ms
20 ms
20 ms
With manual start
max.
30 ms
30 ms
30 ms
30 ms
Delay-on de-ener-
gisation
With power failure
typ. UB 240 V
–
140 ms
–
140 ms
With power failure
max. UB 240 V
–
155 ms
–
155 ms
With power failure
typ. UB 120 V
–
35 ms
–
35 ms
With power failure
max. UB 120 V
–
40 ms
–
40 ms
After safety func-
tion is triggered
typ.
20 ms
20 ms
20 ms
20 ms
After safety func-
tion is triggered
max.
30 ms
30 ms
30 ms
30 ms
Recovery time at
max. switching fre-
quency 1/s
After power fail-
ure
1500 ms
1500 ms
1500 ms
1500 ms
After safety func-
tion is triggered
1000 ms
1000 ms
1000 ms
1000 ms
Supply interruption
before de-energisa-
tion
20 ms
10 ms
20 ms
10 ms
Simultaneity, chan-
nel 1 and 2 max.
3-8 s
3-8 s
3-8 s
3-8 s
Environmental data 750600
750601
751600
751601
Climatic suitability
EN 60068-2-1, EN
60068-2-14, EN
60068-2-2, EN
60068-2-78
EN 60068-2-1, EN
60068-2-14, EN
60068-2-2, EN
60068-2-78
EN 60068-2-1, EN
60068-2-14, EN
60068-2-2, EN
60068-2-78
EN 60068-2-1, EN
60068-2-14, EN
60068-2-2, EN
60068-2-78