PNOZ s60
Operating Manual PNOZ s60
1004492-EN-01
| 15
Legend
}
S1: Start button
Operation
When the relay outputs are switched on, the mechanical contact on the relay cannot be
tested automatically. Depending on the operational environment, measures to detect the
non-opening of switching elements may be required under some circumstances.
When the product is used in accordance with the European Machinery Directive, a check
must be carried out to ensure that the safety contacts on the relay outputs open correctly.
Start the device again or open the safety contacts (switch off output), so that the internal
diagnostics can check the correct opening of the safety contacts
}
for SIL CL 3/PL e at least 1x per month
}
for SIL CL 2/PL d at least 1x per year
NOTICE
The safety function should be checked after initial commissioning and each
time the plant/machine is changed. The safety functions may only be
checked by qualified personnel.
NOTICE
If the measuring voltages are below the set switching threshold for longer
than 24 hours, the PNOZ s60 must be restarted (switch the supply voltage
off and on).
Status indicators
INFORMATION
Several status indicators and error indicators may occur simultaneously.
The unit is ready for operation when the Power LED is permanently lit.
LEDs indicate the status and errors during operation:
LED on
LED flashes
LED off