Pilz 750600 Скачать руководство пользователя страница 1

PNOZ s60

Operating Manual-1004492-EN-01

}

Safety relays

Содержание 750600

Страница 1: ...PNOZ s60 Operating Manual 1004492 EN 01 Safety relays...

Страница 2: ...nta tion will be gratefully received Source code from third party manufacturers or open source software has been used for some components The relevant licence information is available on the Internet...

Страница 3: ...ity 6 Disposal 6 For your safety 6 Unit features 7 Safety features 7 Block diagram terminal configuration 8 Function description 8 Installation 10 Wiring 11 Preparing for operation 12 Operation 15 Sta...

Страница 4: ...rly important is identified as follows DANGER This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventive measures...

Страница 5: ...roduct Use of the product outside the areas described in this manual Use of the product outside the technical details see Technical details 18 NOTICE EMC compliant electrical installation The product...

Страница 6: ...generic and specialist standards applicable to the specific application Warranty and liability All claims to warranty and liability will be rendered invalid if The product was used contrary to the pu...

Страница 7: ...onitor external contactors or switch disconnectors Protective separation between the external voltage supply and the hazardous voltage cir cuits Plug in connection terminals either spring loaded termi...

Страница 8: ...Y5 and the measuring voltages must be connected to the measuring circuit L1 L2 L3 When the supply voltage is applied the POWER LED will light Input circuit Y4 Y5 is open contactor active or switch di...

Страница 9: ...the measuring voltage 64 V Table of functions Automatic start start circuit S33 34 is closed The supply voltage is connected Base unit only excluding expansion modules If the N O contact of the safet...

Страница 10: ...Low Installation Install base unit without contact expansion module Ensure that the plug terminator is inserted at the side of the unit Connect base unit and PNOZsigma contact expansion module Remove...

Страница 11: ...arate multicore cables must be used for the measuring voltages L1 L2 L3 N and the measuring voltages L1 L2 L3 N NOTICE Ensure that there is sufficient fuse protection for the connection cables at term...

Страница 12: ...protected from mechan ical damage e g by installing them in a conduit A SELV PELV voltage source can be connected to 24 VDC external supply voltage En sure that there is sufficient fuse protection fo...

Страница 13: ...voltage N Measuring circuit single phase measurement Measuring voltage L1 L1 N L2 L3 L1 L1 L1 N L1 N L2 L3 L1 L1 L1 N Start circuit Automatic start Manual start S1 Feedback loop with feedback loop mon...

Страница 14: ...tion to PNOZsigma contact expansion modules PNOZ s7 PNOZ s7 1 PNOZ s7 2 PNOZ s8 PNOZ s10 PNOZ s11 The input circuit is connected and evaluated via the connector PNOZ s60 The wiring will differ if you...

Страница 15: ...output so that the internal diagnostics can check the correct opening of the safety contacts for SIL CL 3 PL e at least 1x per month for SIL CL 2 PL d at least 1x per year NOTICE The safety function s...

Страница 16: ...voltage see Function description 8 Faults malfunctions The PLAUSIBILITY CHECK LED lights Measuring voltage is lower than the switching threshold although input circuit Y4 Y5 is open The SYSTEM FAULT L...

Страница 17: ...PNOZ s60 Operating Manual PNOZ s60 1004492 EN 01 17 Dimensions 96 3 78 98 3 86 90 3 54 120 4 72 Fig Dimensions in mm...

Страница 18: ...DC 7 5 W 8 W 7 5 W 8 W Frequency range AC 50 60 Hz 50 60 Hz 50 60 Hz 50 60 Hz Duty cycle 100 100 100 100 Measuring circuit 750600 750601 751600 751601 Min measuring voltage 110 V 110 V 110 V 110 V Ma...

Страница 19: ...back loop 0 1 A 0 1 A 0 1 A 0 1 A Pulse duration feedback loop 150 ms 150 ms 150 ms 150 ms Semiconductor outputs 750600 750601 751600 751601 Number 6 6 6 6 Voltage 24 V 24 V 24 V 24 V Current 50 mA 50...

Страница 20: ...500 VA 1500 VA DC1 at 24 V 24 V 24 V 24 V Min current 5 mA 5 mA 5 mA 5 mA Max current 6 A 6 A 6 A 6 A Max power 144 W 144 W 144 W 144 W Utilisation category of auxiliary contacts AC1 at 250 V 250 V 25...

Страница 21: ...h the standard EN 60947 5 1 EN 60947 5 1 EN 60947 5 1 EN 60947 5 1 Max melting in tegral 66 A s 66 A s 66 A s 66 A s Blow out fuse quick 6 A 6 A 6 A 6 A Blow out fuse slow 4 A 4 A 4 A 4 A Blow out fus...

Страница 22: ...UB 120 V 35 ms 35 ms With power failure max UB 120 V 40 ms 40 ms After safety func tion is triggered typ 20 ms 20 ms 20 ms 20 ms After safety func tion is triggered max 30 ms 30 ms 30 ms 30 ms Recover...

Страница 23: ...Test severity class Class 1 Class 1 Class 1 Class 1 Shock stress In accordance with the standard EN 60255 21 2 EN 60255 21 2 EN 60255 21 2 EN 60255 21 2 Test severity class Class 1 Class 1 Class 1 Cl...

Страница 24: ...ss sec tion flexible with crimp connectors no plastic sleeve 0 25 1 mm 24 16 AWG 0 25 1 mm 24 16 AWG 2 core with the same cross sec tion flexible without crimp connectors or with TWIN crimp connectors...

Страница 25: ...TION A safety function s SIL PL values are not identical to the SIL PL values of the units that are used and may be different We recommend that you use the PAScal software tool to calculate the safety...

Страница 26: ...ig Service life graphs at 24 VDC and 230 VAC Example Inductive load 0 2 A Utilisation category AC15 Contact service life 1 000 000 cycles Provided the application to be implemented requires fewer than...

Страница 27: ...suring voltage Phase Phase Phase Neutral Max operating voltage Max voltage at the out put relays 3000 m 300 V 150 V 150 V 4000 m 300 V 150 V 150 V 5000 m 150 V 150 V 150 V Reduction of the max measuri...

Страница 28: ...ug 10 pieces Connector for terminating a PNOZsigma base unit or PNOZsigma expansion module 10 pieces 750 010 PNOZ s connector 10 pieces Connector for connecting a PNOZsigma base unit to a PNOZsigma ex...

Страница 29: ...etyNET p THE SPIRIT OF SAFETY are registered and protected trademarks of Pilz GmbH Co KG in some countries We would point out that product features may vary from the details stated in this document de...