PSEN opII3B Series
Operating Manual PSEN opII3B Series
1004845-EN-02
| 31
}
A test pulse lasting no longer than 300 µs is bridged
Suitable Pilz evaluation devices are, for example:
}
PNOZelog for monitoring safety light curtains
}
PNOZsigma for monitoring safety light curtains
}
PNOZ X for monitoring safety light curtains
}
PDP67 ION and PDP67 ION HP
– Connect the OSSDs on the receiver to pins 2 and 4 on the PDP67 ION.
– Ensure that pins 1 and 5 on the PDP67 ION are used as an ST output.
– Make the connection using one of the cables listed in the order reference (see
reference for accessories, connection to PDP67 [
).
}
PNOZmulti for safety light curtain monitoring
Configure the safety light curtain in the PNOZmulti Configurator with switch type 3.
}
Automation system PSS 4000 for monitoring safety light curtains with the FS_LightCur-
tain function block
The correct connection to the respective evaluation device is described in the operating
manual for the evaluation device. Connect the evaluation device according to the specifica-
tions in the selected evaluation device’s operating manual.
5
3
1
2
4
5
3
1
0 V
24 V
0 V
OSSD 1
OSSD 2
0 V
24 V
24 V
24 V
24 V
T
x
R
x
uncoded
uncoded
uncoded
uncoded
PSENopII
receiver
PSENopII
transmitter
Evaluation device
Input circuit
External
supply voltage
Fig.: Dual-channel connection of an uncoded safety light curtain at the input circuit of an evaluation device